− 23 −
2-3 Multi port FS unit
Models : RBM-Y0611F4PUL, RBM-Y0611F6PUL
17.4"(440)
22.4"(567)
0.9"(21)
6.0"(152) 0.8"(18)
4.8"(120)
2.6"(65)
6.3"(160)
1.3"(33)
6.0"(150)
6.3"(160)
6.3"(160)
1.0"(25)
8.1"(205)
1.3"(33)
(Hanging bolt pitch)
A
B
(Hanging bolt pitch)
(Unit external dimension)
(Unit external dimension)
Pitch
Gas pipe
Liquid pipe
Control Box
(Hang-up
plate bottom)
Discharge gas pipe
Suction gas pipe
Liquid pipe
Drain socket
Refrigerant pipe connecting port
7.6"(192)
4.8"(121)
10.4"(263)
12.5"(315)
1.5"(36)
1.0"(25)
1.3"(32)
3.5"(88)
5.2"(130)
8.5"(215)
Refrigerant pipe connecting port
outdoor unit side
1
indoor unit side
2
Flow selector unit
indoor unit
33ft(10m) or more
Avoid installing the unit at a place with quiet background sound as follows.
(1)Rooms with quiet background such as bed room, hospital, or room in a hotel.
(2)Rooms which have no ceiling and a fabric does not block the residence space from the Flow Selector unit.
(3)Rooms which have opening port at the ceiling.
When installing the unit at the above places,separate the unit from the indoor unit (more than 33ft(10m)) and
install the unit at a place so that sound does not transmit into the room such as in the corridor ceiling.
Refer to the installation manual about other cautions for selection of installation place.
3.7"(94) (1.3"(33))
RBM-Y0611***
A B
F4PUL
28.8"(730) 31.6"(802)
F6PUL
41.4"(1,050) 44.2"(1,122)
3.0"(76)
Pitch
Installation constraints
Power supply cable intake port
(Φ3/4"(Φ22))
Drain pipe connecting port
(size VP20)
Communication cable intake port
(Φ1/2"(Φ13))
Unit: in (mm)
2.0"(50) or more
Enough space to
connect the site pipe
2.0"(50) or more
Control Box
Check port
17.7"(450) or more
23.7"(600) or more
Service hole
17.7"(450)
Service hole
17.7"(450)
2.8"(70)
21.7"(550) or more
21.7"(550) or more
4.0"(100) or more
6.0"(150) or more
■Installation space
RBM-Y0611***
Outdoor unit side
(Upstream)
Indoor unit side
(Downstream)
Suction gas pipe
Discharge gas pipe
Liquid pipe
gas pipe
Liquid pipe
F4PUL
Φ1-1/2" Φ1-1/8" Φ7/8" Φ5/8" Φ3/8"
F6PUL
■Specifcations
■Connection pipe size of FS unit (default)
Outdoor unit
downstream
Outdoor unit
FS unit
FS unit
indoor unit
indoor unit
(2)
(1)
(1)
(2)
(3) (4) (3) (4) (2)
(2)
One Indoor unit connection
Multi Indoor unit connection
Outdoor unit side pipe size (1)
Total capacity codes of indoor units
at the downstream side
Pipe size
Suction gas pipe
Discharge gas pipe
Liquid pipe
Below 61
Φ5/8" Φ1/2" Φ3/8"
61 to below 115.5
Φ7/8" Φ3/4" Φ1/2"
115.5 to below 153.5
Φ1-1/8" Φ7/8" Φ5/8"
153.5 to below 191.5
Φ1-1/8" Φ7/8" Φ3/4"
191.5 to below 239
Φ1-3/8" Φ1-1/8" Φ3/4"
239 to below 334
Φ1-3/8" Φ1-1/8" Φ7/8"
334 or more
Φ1-5/8" Φ1-3/8" Φ7/8"
Indoor unit side pipe size (2)
Indoor unit side pipe size (3)
Total capacity codes of indoor units
at the downstream side
Pipe size
Below 61
Gas pipe
Liquid pipe
Φ5/8" Φ3/8"
Y-shaped branching joint (4)
Total capacity codes of indoor units
at the downstream side
Y-shaped branching joint Model name
Below 61
RBM-BY55UL
Connectable indoor units of 1 port: 61kBtu/h or less and 8 units or less.
■Piping dimensions
1
2
1
Bolt size : 4-M0.4"(10)
(field supply)
Indoor unit capacity code
Gas side
Liquid side
007 to 012 type
Pipe length
(Actual length)
49ft(15m) or less
Φ3/8" Φ1/4"
Over 49ft(15m)
Φ1/2" Φ3/8"
015 to 018 type
Pipe length
(Actual length)
49ft(15m) or less
Φ1/2" Φ1/4"
Over 49ft(15m)
Φ5/8" Φ3/8"
021 to 054 type
Φ5/8" Φ3/8"