30 P9 ASD Quick Start Guide
Standard Startup Wizard Parameter Requirements
The Standard Startup Wizard queries the user for information on the I/O signal parameters, control, and
the EOI display settings of the ASD. The ASD may also be setup by directly accessing each of the startup
settings via the Program menu or the associated Direct Access Numbers (See the P9 ASD Installation
and Operation Manual for more information on the Direct Access Numbers).
Voltage and Frequency Rating of the Motor (F409/F014)
Motors are designed and manufactured to be operated within a specific voltage and frequency range. The
voltage and frequency specifications for a given motor may be found on the name-plate of the motor.
Highlight and click the voltage and frequency of the motor being used.
Upper-Limit Frequency (F012)
This parameter sets the highest frequency that the ASD will accept as a frequency command or frequency
setpoint. The ASD may output frequencies higher than the Upper-Limit Frequency (but, lower than the
Maximum Frequency) when operating in the PID Control mode, Torque Control mode, or the Vector
Control modes (sensorless or feedback).
Lower-Limit Frequency (F013)
This parameter sets the lowest frequency that the ASD will accept as a frequency command or frequency
setpoint. The ASD will output frequencies lower than the Lower-Limit Frequency when accelerating to
the lower-limit or decelerating to a stop. Frequencies below the Lower-Limit may be output when
operating in the PID Control mode, Torque Control mode, or the Vector Control modes (sensorless or
feedback).
Automatic Acceleration/Deceleration (F000)
When Automatic ACC/DEC is chosen, the ASD adjusts the acceleration and deceleration rates according
to the applied load. The minimum accel/decel time may be set using F508. The motor and the load must
be connected prior to selecting Automatic Accel/Decel.
Select Manual to allow the settings of F009 and F010 to control the accel/decel, respectively. The
acceleration and deceleration times range from 12.5% to 800% of the programmed values for the active
acceleration time.
Select Automatic ACC Only to allow for the acceleration rate to be controlled automatically only.
Acceleration Time (F009)
This parameter specifies the time in seconds for the output of the ASD to go from 0.0 Hz to the Maximum
Frequency for the 1 Acceleration profile. The Accel/Decel Pattern may be set using F502.
Deceleration Time (F010)
This parameter specifies the time in seconds for the output of the ASD to go from the Maximum
Frequency to 0.0 Hz for the 1 Deceleration profile. The Accel/Decel Pattern may be set using F502.