Virtual Linear Pump Setup
Q9 Plus ASD Install/Op Manual
https://www.toshiba.com/tic/ 65
Figure 35. Complete the virtual linear pump setup.
1. Press the Stop key.
2. The motor decelerates to a stop at the pro-
grammed rate.
3. Click Next to continue (available once reach-
ing zero Hz).
Figure 36. Select an Operating Mode.
Press ESC
1. Select the Virtual Linear Pump operating mode.
2. Select Direct Mode if using no feedback or
select Process Hold if using feedback.
3. Click Save/Exit.
4. While in the Local mode, press Run.
While running, adjust parameters F500 and F501
to stabilize operation if unstable.