CMOD/FMOD Control
Q9 Plus ASD Install/Op Manual
34 https://www.toshiba.com/tic/
Possible frequency control source selections
include the following (F004):
V/I,
RR,
RX,
EOI Keypad,
RS485/BACnet,
Communication Option Board,
RX2 Option (Option AI1),
V/I Option (Option AI2),
UP/DOWN Frequency,
RP Pulse Input Option, or
High-Speed Pulse Input Option.
Note: See Table 9 on page 252 for the
available discrete input terminal
functions that may override the F003
and F004 selections as shown in
Figure 28. (i.e., Serial/Local Switch,
Fire Speed, etc.).
Command and Frequency Control
Selections
Any or all of the command and frequency control
sources may be selected and used to control the
output speed of the ASD or switched to another
source as a function of a user-selected condition.
Placing the Q9 Plus ASD in the Local mode (Local/
Remote LED on) selects the EOI Keypad as the
control selection for command and frequency input.
Figure 28. Command- and Frequency-Control Source Relationship.