Direct Access Parameter Information
Q9 Plus ASD Install/Op Manual
Command Mode
Program Fundamental Standard Mode Selection
The Command Mode Selection establishes the source of the
command input for the ASD. Command inputs include Run, Stop,
Forward, etc. The Override feature may supersede the Com-
mand Mode Selection setting (see Command Mode and Fre-
quency Mode Control on pg. 33).
Settings:
0 — Terminal Board
2 — EOI Keypad
3 — RS485/BACnet
4 — Communication Option Board
Direct Access Number
F003
Parameter Type — Selection List
Factory Default — Terminal
Board
Changeable During Run — No
Frequency Mode 1
Program Fundamental Standard Mode Selection
The Frequency Mode 1 setting establishes the source of the fre-
quency-control input for the ASD. The Frequency Mode 2 setting
or the Override feature may supersede the Frequency Mode 1
setting.
Note: Only Bolded items from the Settings list below may be
placed in the Override Mode. See the section titled
Command Mode and Frequency Mode Control on pg. 33 for
additional information on the Override feature.
Settings:
1 — V/I
2 — RR
3 — RX
5 — EOI Keypad
6 — RS485/BACnet
7 — Communication Option Board
8 — RX2 (AI1 Option)
9 — Option V/I (AI2 Option)
10 — UP/DOWN Frequency
11 — Optional RP Pulse Input
12 — Optional High-Speed Pulse Input
Direct Access Number
F004
Parameter Type — Selection List
Factory Default — RR
Changeable During Run — No