6
90
RoughnessObliquity Warp
Indoor Unit Fixing
•  For detaching the indoor unit from the 
installation plate, pull the indoor unit 
toward you while pushing its bottom up 
at the specifi ed parts.
1.  Pass the pipe through the hole in the wall and hook the indoor unit on the 
installation plate at the upper hook.
2.  Swing the indoor unit to right and left to confi rm that it is fi rmly hooked up 
on the installation plate.
3.  While pressing the indoor unit onto the wall, hook it at the lower part on 
the installation plate. Pull the indoor unit toward you to confi rm that it is 
fi rmly hooked up on the installation plate.
Drainage
1.  Run the drain hose sloped downwards.
2.  Put water in the drain pan and make sure that the water is drained out of 
doors.
3. When connecting extension drain hose, insulate the connecting part of 
extension drain hose with shield pipe.
  NOTE
•  The hole should be made at a slight downward slant on the outdoor side.
Arrange the drain pipe for proper drainage from the unit.
Improper drainage can result in dew-dropping.
This air conditioner has the structure designed 
to drain water collected from dew, which forms 
on the back of the indoor unit, to the drain pan. 
Therefore, do not store the power cord and other 
parts at a height above the drain guide.
CAUTION
OUTDOOR UNITOUTDOOR UNIT
Installation Place
•  A place which provides the spaces around the outdoor unit as shown in the 
diagram
•  A place which can bear the weight of the outdoor unit and does not allow an 
increase in noise level and vibration
•  A place where the operation noise and discharged air do not disturb your 
neighbors
•  A place which is not exposed to a strong wind
•  A place free of a leakage of combustible gases
•  A place which does not block a passage
•  When the outdoor unit is to be installed in an elevated position, be sure to 
secure its feet.
•  The allowable pipe length is up to 20 m. If the length is over 15 m, add 20 g 
of refrigerant for every additional meter of the pipe length for all models.
•  The allowable height of outdoor-unit installation site is up to 10 m.
•  A place where the drain water does not raise any problems
CAUTION
1.  Install the outdoor unit without anything blocking the air discharging.
2.  When the outdoor unit is installed in a place always exposed to strong 
wind like a coast or on a high storey of a building, secure the normal fan 
operation using a duct or a windshield.
3.  In particularly windy areas, install the unit such as to avoid admission of 
wind.
4.  Installation in the following places may result in trouble.
  Do not install the unit in such places.
  •  A place full of machine oil
  •  A saline-place such as the coast
  •  A place full of sulfi de gas
  •  A place where high-frequency 
waves are likely to be generated 
as from audio equipment, welders, 
and medical equipment
Refrigerant Piping Connection
1.  Cut the pipe with a pipe cutter.
2. Insert a fl are nut into the pipe and fl are the pipe.
 • Projection margin in fl aring : A (Unit : mm)
Rigid (clutch type)
Imperial (wing nut type)
Outer dia. of copper pipe R410A
Ø6.35
1.5 to 2.0
Ø9.52
1.5 to 2.0
Outer dia.
of copper pipe
R410A tool used
Conventional tool 
used
Ø6.35
0 to 0.5 1.0 to 1.5
Ø9.52
0 to 0.5 1.0 to 1.5
     Flaring
1
2
1
Hook here.
Installation plate
Hook
Press
(unhook)
Push Push
Do not form the
drain hose into
a wavy shape.
Do not rise the
drain hose.
50 mm
or more
Do not put the
drain hose end
into water.
Do not put the
drain hose end
in the drainage ditch.
Shield pipe
Inside the room
Drain hose
Extension drain hose
Wall
Drain
guide
Space for pipes
Strong 
wind
A
Die
Pipe
01_1115551106-EN.indd   601_1115551106-EN.indd   6 6/19/2557 BE   2:25 PM6/19/2557 BE   2:25 PM