(Table 2) Indoor fan air flow rate <Heating>
Fan speed
level
Fan speed Air flow rate Fan speed Air flow rate Fan speed Air flow rate
(rpm) (m3/h) (rpm) (m3/h) (rpm) (m3/h)
WF UH 560 528 600 570
700 675
WE H
560 528
580 552
700 675
WD M+
480 443 520 486 590 570
WC 440 408
470 435
570 540
WB M
400
366 460 426 500 467
WA 380 342 410 376 460 426
W9 L+
370 334 400 366
460 426
W8 L
320 282
340 300 400 366
W7 L- 260 216 270 228 360 324
W6 260 216 270 228 340 300
W5 UL 260 216 270 228 340 300
W4 260 216 270 228 340 300
W3 260 216 270 228 340 300
W2 SUL 240 198 250 210 320 282
W1 240 198 240 198 240 198
HEAT
Item
Operation flow and applicable data, etc. Description
[In starting and in stability]
FAN AUTO
FAN Manual
In starting
• Until 12 minutes passed after operation start
• When 12 to 25 minutes passed after operation
start and room temp. is 3°C or lower than set temp.
• Room temp. < Set temp. –4°C
In stability
• When 12 to 25 minutes passed after operation start
and room temp. is higher than (set temp. –3°C)
• When 25 minutes or more passed after operation start
• Room temp. = Set temp. –3.5°C
RAS-B13J2FVG-E
RAS-B18J2FVG-E
RAS-B10J2FVG-E
2. Indoor fan
motor control