Item
Operation flow and applicable data,etc
Description
25. Outdoor
control
Quiet
<With Quiet control/Non-select method>
1. Purpose
For the users who concern about noise
the outdoor unit, this control control the
max revolutions of the compressor to
reduce the noise
2. Description
To reduce noise, [RESET] button of the
indoor unit is kept pushed for 20
seconds.
The number of revolution for the indoor
fan motor and the set up temp value
are kept as they are.
3. Operation
As show in the table, the maximum
revolution number of indoor unit
compressor can be reduced.
As the maximum number of revolution
of the compressor is restricted, the
rise-up performance at the start time is
weakened.
Select "Conrol" or "No conrol" by keeping
[RESET] button pushed for 20 seconds.
("No control" at shipment from the factory.)
Exchanging from "No control" to "Control" :
Beep sound is heard (Pi, Pi, Pi, Pi, Pi) and
the operation LED 5Hz flashes for 5
seconds.
Exchanging from "Control" to "No control" :
Beep sound is heard.
(Operation LED does not flash.)
<Maximum number of revolution of compressor at normal time and Quiet control time>
RAS-B10J2FVG-E RAS-B13J2FVG-E
Quiet controlled
(rps)
COOL
78
44
86
44
−5°C ~
102
23
100
23
HEAT
−10 ~ −5°C ~
102
23
100
23
−10°C ~
102
23
100
23
Outside temp.
(TO)
Normal time
(rps)
Normal time
(rps)
Quiet controlled
(rps)
26.
Operation
mode
setectable
2.
1.
Purpose
Choosing the operating system as
appropriate in real condition
Operation
Factory default setting prefer
"Heat pump" system. Through it is
able to cooling only system heating
only system or return to factory
default.
RAS-B18J2FVG-E
Quiet controlled
(rps)
83
49
83
23
83
23
83
23
Normal time
(rps)
Operating system setting
•
•
•
Do cut J804 for cooling only system
Do cut J805 for heating only system
Do cut both of J804 and J805 for return
to factory default.
For RAS-10, 13J2AVSG-E
For RAS-18J2AVSG-E