118
8-7-3. Error Clearing Function
1. Clearing from the main remote controller
[Error clearing in outdoor unit]
Error of the outdoor unit is cleared by the unit of one refrigerant circuit system to which the indoor units oper-
ated by the remote controller. (Error of the indoor unit is not cleared.)
For clearing errors, the service monitor function of the remote controller is used.
<Method>
1
Change the mode to service monitor mode by pushing
CL
+ buttons simultaneously for
4 seconds or more.
2
Using / buttons, set “FF” to item code.
The display in Section A in the following figure is counted with interval of 5 seconds as
“
0005 ”
→→
→→
→ “0004 ”
→→
→→
→ “0003 ”
→→
→→
→ “0002 ”
→→
→→
→ “0001 ”
→→
→→
→ “0000 ”.
When the count arrives “0000 ”, the error is cleared.
∗ However, counting from “0005 ” is repeated on the display.
3
When button is pushed, the status returns to the normal status.
[Error clearing in indoor unit]
Error in the indoor unit is cleared by button on the remote controller.
(Only error of the indoor unit connected with operating remote controller is cleared.)
UNIT
SET
CL
UNIT No.
CODE No.
R.C. No.
Operation procedure
1 2 3
The status returns to the normal status.
2
1
3
Section A