Check code
[F01] / [0F]
(d07 / AI-NET)
Check code name
Indoor TCJ sensor error
Cause of operation
TCJ sensor Open/Short
Check code
[F02] / [0d]
(d07 / AI-NET)
Check code name
Indoor TC2 sensor error
Cause of operation
TC2 sensor Open/Short
YES
YES
NO
NO
Correct connection of connector.
Replace TCJ sensor.
Correct connection of connector.
Replace TC2 sensor.
Is TCJ sensor connector (CN102: Red)
on indoor P.C. board normally connected?
Are characteristics of TCJ sensor
resistance value normal?
Check indoor main P.C. board.
Defect Replace
Is TC2 sensor connector (CN101: Black)
on indoor P.C. board normally connected?
Are characteristics of TC2 sensor
resistance value normal?
Check indoor main P.C. board.
Defect Replace
YES
YES
NO
NO
Indoor unit temperature sensor characteristics
See Characteristics-2.
Indoor unit temperature sensor characteristics
See Characteristics-2.