Toshiba Super MMY-MAP0801HT8 - Additional Amount of Refrigerant; Additional Amount of Refrigerant by Pipe Length; Corrective Amount of Refrigerant by System Capacity

Toshiba Super MMY-MAP0801HT8
270 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
91
Pipe dia at
liquid side
Ø6.4
Ø9.5
Ø12.7
Ø15.9
Ø19.0
Ø22.2
Standard amount of refrigerant
kg/m
0.025 ×
0.055 ×
0.105 ×
0.160 ×
0.250 ×
0.3505 ×
Total pipe length at each liquid side
=
=
=
=
=
=
Additional amount of refrigerant by pipe
length (A)
Additional amount of refrigerant pipe
dia at each liquid side kg
kg
kg
kg
kg
kg
kg
kg
System horse
power HP
5
6
8
10
12
14
16
18
20
22
22
24
24
26
Unit Unit Unit Unit
1234
5
6
8
10
12
86
88
10 8
10 10
886
12 10
888
12 12
10 8 8
Corrective amount
of refrigerant (C) kg
0
0
1.5
2.5
3.5
0
0
0
3.0
0
5.0
4.0
7.0
4.0
System horse
power HP
28
30
32
32
34
34
36
36
38
40
42
44
46
48
Normal type
Unit Unit Unit Unit
1234
10 10 8
10 10 10
8888
12 10 10
10888
12 12 10
10 10 8 8
12 12 12
10 10 10 8
10 10 10 10
12 10 10 10
12 12 10 10
12 12 12 10
12 12 12 12
Corrective amount
of refrigerant (C) kg
2.0
0
6.0
1.0
6.0
3.0
6.0
4.0
6.0
5.0
4.0
2.0
0
2.0
Lastly add the additional amount of refrigerant by pipe length (A) to the corrective amount of refrigerant by
system capacity (C). It is the final additional amount of refrigerant.
As the result, If minus sign is indicated, do not add the refrigerant (=0kg).
<Additional amount of refrigerant>
Additional amount of refrigerant by pipe length (A)
Corrective amount of refrigerant by system HP (C)
Additional amount of refrigerant
kg
kg
kg
Next, refer to the following table for the corrective amount of refrigerant (C) by system capacity.
<Corrective amount of refrigerant by system capacity>
Normal type
Check the additional amount of refrigerant.
<Check list 2>
Calculate the additional amount of refrigerant from the additional amount of refrigerant (A) by the pipe diam-
eter at liquid side and the pipe length to be connected and the corrective amount of refrigerant (C) by the
system capacity.
Additional amount
=
Actual liquid
×
Additional amount of
+
Corrective amount of
of refrigerant pipe length refrigerant per liquid pipe 1m refrigerant by system capacity
(A) (C)
Firstly enter the total length for each liquid pipe in the following table, and then calculate the additional amount
of refrigerant by pipe length.
<Additional amount of refrigerant by pipe length>