Check code
Main
remote
controller
L30
P01
P03
P04
P05
Outdoor 7-segment display
Check code
Sub-code
L30 Detected indoor address
L31
——
P03
P04 01: Compressor 1 side
02: Compressor 2 side
P05 01: Power supply open
phase
02: Power supply negative
phase
AI-NET
central control
remote controller
b6
11
1E
21
AF
Detected
position
Indoor
I/F
Indoor
I/F
I/F
I/F
Check code name
Interlock in indoor unit
from outside
Extended IC (Integrated
Circuit) error
Indoor fan motor error
Discharge temp TD1
error
Actuation of high-
pressure SW
Open phase negative
phase
Status
Corresponding
unit only stops.
Operation
continues.
Corresponding
unit only stops.
All stop
All stop
All stop
Error detection condition
Outside error input terminal
Detected signal to (CN80) for
more 1 minute
P.C. board (I/F) parts error
Discharge temp (TD1) exceeded
115°C.
High-pressure SW actuated.
Open phase was detected when
the power turned on.
Negative phase was detected
when the power turned on.
Check item (position)
n Outside device is connected to connector (CN80):
1) Check outside device error.
2) Check indoor P.C. board error.
n Outside device is not connected to connector
(CN80):
1) Check indoor P.C. board error.
Check indoor (I/F) P.C. board.
Check the lock of fan motor (AC fan).
Check cabling.
Check full opening of outdoor service valves
(Gas side, Liquid side).
Check clogging of outdoor PMV. (PMV1,2)
Check characteristics of TD1 sensor resistance value.
Check refrigerant shortage.
Check 4-way valve error.
Check leakage of SV41 circuit.
Check SV4 circuit.
(Miscabling and misinstallation of SV41 and SV42)
Check Pd pressure sensor error.
Check full opening of outdoor service valves
(Gas side, Liquid side).
Check outdoor fan error.
Check outdoor fan motor error.
Check clogging of outdoor PMV. (PMV1,2)
Check clogging of indoor/outdoor heat exchangers.
Check short-circuiting of outdoor suction/discharge
air.
Check clogging of SV2 circuit.
Check outdoor P.C. board (I/F) error.
Check indoor fan system error.
(Cause of air volume decrease)
Check opening of indoor PMV.
Check miscabling of communication line between
indoor and outdoor.
Check operation error of check valve of discharge
pipe.
Check SV4 valve circuit.
Check SV5 valve circuit.
Check refrigerant overcharge.
Check outdoor power line.
Check outdoor P.C. board (I/F) error.