146
Check code
Main
remote
controller
P26
P29
P31
Outdoor 7-segment display
Check code
Sub-code
P26 01: Compressor 1 side
02: Compressor 2 side
P29 01: Compressor 1 side
02: Compressor 2 side
——
AI-NET
central control
remote controller
14
16
47
Detected
position
IPDU
IPDU
Indoor
Check code name
G-Tr short-circuit
protection error
Compressor
position detection
circuit error
Other indoor error
(Group follower
unit error)
Status
All stop
All stop
Corresponding
unit only stops.
Error detection condition
Instantaneous over-current
was detected when compres-
sor started.
Position was not normally
detected.
E07/L07/L03/L08 was
detected when other indoor
unit in the group was defective.
Check item (position)
Check connector connection and wiring on IPDU P.C. board.
Check compressor error and defect of compressor coil.
Check outdoor P.C. board (IPDU) error.
Check connector connection and wiring.
Check compressor error and defect of compressor coil.
Check P.C. board (IPDU) error.