Table A-2 General Specifications (EN751, EN751A, EN761, FN711)
Item
Specifications
EN751A EN751 EN761 FN711
Working temperature range 
(Product ambient temperature)
Vertical installation: 0 to 55
o
C
Working humidity range 10 to 95% RH  (without condensation)
Storage temperature range
-25 to 70
o
C
Storage humidity range 5 to 95% RH   (without condensation)
Source voltage range 4.75 to 5.25 VDC (Rated voltage :5.0VDC)
Current drain 
(at rated power input)
1.1 A or less
(5.0VDC)
1.8A or less
(5.0VDC)
Power consumption 
(at rated power input)
5.5W or less 9W or less
Insulation resistance (between 
signal and F.G.)
10 megohms or more
Withstand boltage 
(between signal and F.G.)
500 VAC for 1 minute
Dust
0.3 mg/m
3
 or less
Vibration resistance
4.9m/s
2
    1.5mm
p-p
Shock resistance
19.6m/s
2
 (3 times with power off)
Grounding Class D (Grounding resistance: 100 ohms or less)
Cooling  Natural air 
cooling
Forced air cooling
Module dimensions 249 (H) × 35 (W) × 112.7 (D) mm