Error
Code
Error Description
11 Inability to process data because of faulty CPU Module Hardware.
20 Fixed Data (ENQ) within relay command is not "05."
21 Faulty transfer number (there is erroneous transfer byte number within the relay command).
23 Erroneous command code.
24 Erroneous subcommand code.
25 Erroneous command-format data byte.
26 Erroneous function-call operand number.
31 Attempting to write data into the field where any writing is prohibited during a sequence
operation or to use the function call (which is protected from any execution) during a sequence
operation.
32 A command that is defeated during a stop continuity is activated during a stop continuity.
33 Attempting to execute a debug function call despite non-debug mode.
34 Access prohibited owing to access-prohibited configuration.
35 Non-executable owing to execution-priority limiting configuration.
36 Non-executable owing to execution-priority limiting configuration by another device.
39 Attempting to start scanning without any reset after writing I/O point-number parameters or I/O
allocation point-number parameters.
3C During a fatal failure, a command has issued that is not executable during a fatal failure.
3D Non-executable due to competing process while a different-factor command is executed.
3E Non-executable command due to reset existence.
3F Non-executable command due to stop duration.
40 Address of a reading/writing command or of "address+data number" of a command is out of
range.
41 Word/byte number is out of range.
42 Non-designated data is sent.
43 Erroneous function/call operand.
52 Though any timer or counter is employed, a command for reading/writing the set/recent values
is issued.
66 No reply is sent from link module with the link exchange No. specified by a relay command
(owing to no existence of specified link module, power OFF, faulty circuit, or etc.).
70 Non-executable module with the link exchange No. specified by a relay command (owing to
erroneous link No. designation or faulty link module).
72 No reply is sent from link module with the link exchange No. specified by relay command (owing
to no existence of specified link module, power OFF, faulty circuit, or etc.).
73 Multiple relay commands were issued to the same link module from the CPU module and the
link module could not process the commands. Send commands again.