15
SWITCH SETTINGS SELECTION NOMINAL AIRFLOW
7-OFF 8-OFF LOW 1400 CFM
7-ON 8-OFF HIGH 1600 CFM
7-OFF 8-ON HIGH 1600 CFM
7-ON 8-ON HIGH 1600 CFM
SWITCH SETTINGS SELECTION NOMINAL AIRFLOW
7-OFF 8-OFF LOW 1050 CFM
7-ON 8-OFF HIGH 1200 CFM
7-OFF 8-ON HIGH 1200 CFM
7-ON 8-ON HIGH 1200 CFM
SWITCH SETTINGS SELECTION NOMINAL AIRFLOW
7-OFF 8-OFF LOW 700 CFM
7-ON 8-OFF HIGH 800 CFM
7-OFF 8-ON HIGH 800 CFM
7-ON 8-ON HIGH 800 CFM
4WCY4048 AIRFLOW WITH AUXILIARY HEAT (CFM)
4WCY4036 AIRFLOW WITH AUXILIARY HEAT (CFM)
4WCY4024 AIRFLOW WITH AUXILIARY HEAT (CFM)
5-OFF 6-OFF NONE 100%
5-ON 6-OFF 45 SEC 100%
5-OFF 6-ON 90 SEC 50%
5-ON 6-ON ** 50-100%
** This ENHANCED MODE selection provides a
ramping up and ramping down of the indoor blower
speed to provide improved comfort, quietness, and
potential energy savings. The Graph below shows
the ramping process
COOLING FAN DELAY OPTIONS
SWITCH SETTINGS DELAY
NOMINAL
AIRFLOW
OFF OFF
50%
80%
100% if necessary
50%
Dehumidify
Fast Coil Cooling
Efficiency
7.5
minutes
3
minutes
1
minute
FAN OPERATION (CFM)
COMPRESSOR OPERATION ON
OFF
as required
4WCY4060 AIRFLOW WITH AUXILIARY HEAT (CFM)
SWITCH SETTINGS SELECTION NOMINAL AIRFLOW
7-OFF 8-OFF LOW 1400 CFM
7-ON 8-OFF HIGH 1600 CFM
7-OFF 8-ON HIGH 1600 CFM
7-ON 8-ON HIGH 1600 CFM
Indoor Blower Performance
SWITCH SETTINGS SELECTION NOMINAL AIRFLOW
7-OFF 8-OFF LOW 1400 CFM
7-ON 8-OFF HIGH 1600 CFM
7-OFF 8-ON HIGH 1600 CFM
7-ON 8-ON HIGH 1600 CFM
4WCY4042 AIRFLOW WITH AUXILIARY HEAT (CFM)
SWITCH SETTINGS SELECTION NOMINAL AIRFLOW
7-OFF 8-OFF LOW 1050 CFM
7-ON 8-OFF HIGH 1200 CFM
7-OFF 8-ON HIGH 1200 CFM
7-ON 8-ON HIGH 1200 CFM
4WCY4030 AIRFLOW WITH AUXILIARY HEAT (CFM)