WSHP-SVX014J-EN
13
Figure 2. Clearance – EXVG/DXVG 0.75 to 6 tons
36"
1"
1"
UNIT FRONT
LEFT
RETURN
TOP/BACK
SUPPLY
1"
1"
24"
UNIT FRONT
36"
RIGHT
RETURN
TOP/BACK
SUPPLY
24"
A 24–inch clearance from other mechanical and electrical equipment (where
shown) is recommended for most unit configurations. This will enable panel
removal from the unit for service/maintenance.
The 24–inch side clearance on EXVG/DXVG 0.75 to 6T models is for
optimal access only. Side clearance is not a requirement as most
components can be accessed from the front of the unit.
A 1–inch minimum clearance between the filter rack and any obstacle is
required for units in a free return application to provide proper air flow to the
air-to-refrigerant coil. A 12–inch minimum clearance between the filter rack
and any obstacle should be provided to properly attached ductwork.
The 1–inch dimension shown in the back of the unit represents the supply
duct collar for the back supply option. This clearance is needed to clear
these flanges.
Unit Dimensions