12
WSHP-SVX014J-EN
Unit Dimensions
Service Clearances
Per NEC requirements, 36 inches of access and working
space shall be provided and maintained around all control
boxes and electrical equipment to permit ready and safe
operation and maintenance of such equipment. Local
codes may require more clearance to electrical equipment.
Check all code requirements prior to unit installation.
Figure 1. Clearances - EXH/DXH 0.75 to 6 tons
14"
14"
14"14"
LEFT RETURN
RIGHT SUPPLY
UNIT FRONT
RIGHT RETURN
BACK SUPPLY
UNIT FRONT
RIGHT RETURN
LEFT SUPPLY
UNIT FRONT
14"
14"
14"
14"
14"
36"
36" 36"
LEFT RETURN
BACK SUPPLY
UNIT FRONT
14"
14"
14"
36"
A minimum 14–inch clearance for servicing the unit is
required for all EXH 0.75 to 6 tons configurations from other
mechanical and electrical equipment (where shown) to
enable panel removal from the unit for service/maintenance
ability. The optimum clearance required is 20 inches.
Notes:
Return air direction (left-hand or right hand) is
NOT field convertible. Units must be ordered
with correct return air side.
For horizontal models, be sure to allow
enough clearance between the condensate
drain and the ceiling to allow for pitching of
the condensate line. See Figure 20, p. 31 for
pitching requirements.