Table 33. EXV/H and DXV/H electric duct heater data (0.75 to 6 tons) (continued)
MODEL EH Size Volts kW
Amps
DXV/H070 Medium 208-230/60/3 8.2/10.0 22.7/25.1
DXV/H070
High
208-230/60/3 12.3/15.0 34.1/37.7
DXV/H070 Low 460/60/3 5.5 6.9
DXV/H070 Medium 460/60/3 9.2 11.5
DXV/H070
High
460/60/3 13.8 17.3
Note: Electric heat performance table with heat rise data
can be found in Installation Instructions (WSHP-
SVN011*-EN).
Table 34. Electrical data - minimum and maximum
Digit 8 Rated Voltage
Hz Ph
Minimum Utilization
Voltage
Maximum Utilization
Voltage
4 460 60 3 414 506
7 265 60 1 239 292
A 208-230 60 1 197 253
B 208-230 60 3 187 253
Electrical Data