BCX-SVX002A-EN
41
Figure 29. Cv adjustments
Table 20. Actuator clip settings
2-way Valve Body
1 2 3- 3 4 4+ 5 5+ 6 N
No Clip
1/2 in. Z2050QS-F Cv 0.1 0.2 0.4 0.6 0.8 1.2 1.4
1/2 in. Z2050QS-J Cv 0.5 0.7 1.2 1.7 2.4 3.4 4.8 5.9
3/4 in. Z2075QS-K Cv
0.5 1 1.5
2.3
(a)
3.3
(a)
4.6
(a)
6.6 9.8
Stroke Time (seconds)
30 37 41 43 49 51 55 58 62 68 75
(a)
This Cv shows the standard Cv offering for 2-way valves
Table 21. PIC with GPM settings
Clip Position for Flow Adjustment (GPM)
1 1+ 2- 2 2+ 3- 3 3+ 4- 4 4+ 5- 5 5+ 6- 6 6+ N- N
No
Clip
1/2in.
Z2050QPT-B
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
1/2in.
Z2050QPT-D
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.2 1.3 1.5 1.6 1.8 2.0
1/2in.
Z2050QPT-F
0.6 0.7 0.8 0.9 1 1.3 1.5 1.7 1.9 2.2 2.5 2.8 3.1 3.3 3.6 4.3
3/4in.
Z2075QPT-G
1.6 1.8 2.1 2.4 2.7 3 3.3 3.7 4 4.4 4.9 5.3 5.8 6.3 6.7 7.2 7.7 9.0
Stroke Time
(sec)
30 33 35 37 39 41 43 45 47 49 51 53 55 58 60 62 64 66 68 75
Dimensions and Weights

Table of Contents