Table 27. Available electric heat (kW)
Electrical
heat(kW)
Voltage
115/
60Hz 1P
208/
60Hz 1P
220/
50Hz
1P
230/
60Hz
1P
240/
50Hz
1P
277/
60Hz
1P
208/
60Hz
3P
230/
60Hz
3P
380/
50Hz 3P
415/
50Hz
3P
460/
60Hz
3P
575/
60Hz 3P
1 Size 12-120
5 Size 18-120 Size 24-120
10 Size 36-120
15 Size 48-120
20 Size 72-120
24
Size 90,120
30
Size 90,120
Notes:
1. Magnetic contactors are standard.
2. Units with electric heat are available with or without door interlocking disconnect switch.
3. Units with electric heat are available with or without line fuses.
4. Units with electric heat must not be run below the minimum cfm listed. Refer to the General Data section for more information.
5. Electric heat is balanced staging: 1 stage = 100 percent, 2 stages = 50 percent/50 percent.
Table 28. Airflow min/max for BCHE/BCVE blower coils
Unit Size 12 18 24 36 48 60 72 90 120
Nominal cfm 400 600 800 1200 1600 2000 2400 3000 4000
Airflow
Minimum cfm 250 375 500 750 1000 1250 1500 1875 2500
Maximum cfm 500 675 1000 1600 2000 2500 3000 4000 5000
Note: Minimum airflow limits apply to units with hot water or electric heat. There is no minimum airflow limit on cooling coil units. Maximum airflow limits are to help prevent
moisture carryover.