BCX-SVX002A-EN
85
Table 29. Motor electrical data
Voltage Voltage range
Rated HP
Weight (lbs)
FLA
115/60/1 104-127 0.5 14.0 7.46
115/60/1 104-127 1.0 19.0 13.30
208/60/1 187-229 0.5 14.0 4.26
208/60/1 187-229 1.0 19.0 7.73
230/60/1 207-253 0.5 14.0 4.26
230/60/1 207-253 1.0 19.0 7.73
277/60/1 249-305 0.5 14.0 3.76
277/60/1 249-305 1.0 19.0 6.73
220/50/1 198-242 0.5 14.0 4.26
220/50/1 198-242 1.0 19.0 7.73
240/50/1 216-264 0.5 14.0 4.26
240/50/1 216-264 1.0 19.0 7.73
208/60/3 187-229 0.5 13.4 2.40
208/60/3 187-229 1.0 17.1 4.60
208/60/3 187-229 1.5 37.5 7.60
208/60/3 187-229 3.0 53.6 11.20
208/60/3 187-229 5.0 56.0 15.80
230/60/3 207-253 0.5 13.4 2.60
230/60/3 207-253 1.0 17.1 4.80
230/60/3 207-253 1.5 37.5 6.50
230/60/3 207-253 3.0 53.6 11.20
230/60/3 207-253 5.0 56.0 15.30
380/50/3 342-418 0.5 13.4 1.20
380/50/3 342-418 1.0 17.1 2.30
380/50/3 342-418 1.5 37.5 4.20
380/50/3 342-418 3.0 53.6 5.30
380/50/3 342-418 5.0 56.0 8.50
415/50/3 374-457 0.5 13.4 1.30
415/50/3 374-457 1.0 17.1 2.40
415/50/3 374-457 1.5 37.5 4.00
415/50/3 374-457 3.0 53.6 5.50
415/50/3 374-457 5.0 56.0 8.40
460/60/3 414-506 0.5 13.4 1.30
460/60/3 414-506 1.0 17.1 2.50
460/60/3 414-506 1.5 37.5 3.30
460/60/3 414-506 3.0 53.6 5.50
460/60/3 414-506 5.0 56.0 7.80
575/60/3 518 - 633 0.5 13.9 1.10
575/60/3 518 - 633 1.0 18.0 2.10
575/60/3 518 - 633 2.3 28.8 2.80
575/60/3 518 - 633 3.5 53.6 4.60
575/60/3 518 - 633 5.0 56.0 6.50
Installation — Electrical