Optional Properties Supported: Max_Requestor, Max_Info_Frames, Description,
Location, Local_Time, Local_Date Writable Properties: Object_Identifier, Object_Name,
Max_Requestor, Location Property Range Restrictions: Object_Identifier May only
write values from 1 to 4,193,999; Location (limited to 64 characters); Max_Requestor
May only write values from 1 to 127
Analog_Input Objects
Optional Properties Supported: Description, Reliability No Writable Properties
Analog_Value Objects
Optional Properties Supported: Description, Reliability
Writable Properties: Only the Present_Value is writable
Property Range Restrictions
AV1: May only write 30078, 21211, 21212 and 16498
AV2: May only write 10, 11, 12, 31 and 40
AV3: May only write values from 5 to 5000
AV4: May only write value 32768
AV5: May only write values from 0.01 to 320.0
AV6: May only write values such that AV6/AV5 is from 82 to 660 (absolute range is
82-32000). To ensure AV6 accepts/rejects the proper values, set AV5 first.
AV7: May only write values 0 and 1
AV8: May only write values from 1 to 99
AV9: May only write values from 1 to 99
AV10: May only write values from 1 to 6
AV11: May only write the value 0 or a value from 1000 to 3276700 in multiples of
100
Binary_Input Objects
Optional Properties Supported: Description, Reliability
No writable properties
Data Link Layer Options
EIA-485 Token Passing, Requestor (Clause 9), Baud Rate(s): 9600, 19200, 38400, 76800,
115200.
Device Address Binding
Static device binding is not supported. No client functionality is included.
Networking Options
None
Character Sets Supported
ANSI X3.4
BACnet Programming Objects
The following tables provide information about BACnet object types and descriptions.
Legend:
R = Read, R/W= Read or Write
NV= Value is stored in non-volatile memory. The value(s) is still available in the event of
power loss or reset.
Units= Lists the physical units that a register holds.
BBAACCnneett PPrrooggrraammmmiinngg