PKG-SVP01B-EN
47
Programming
End of Submenu (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
RTM Alarm Output Diagnostic Assignment Screens
RTM Alarm Output Diagnostic Assignments
Press ENTER to Review or Adjust
1. Pressing the NEXT key will display the following screen.
Assign Diagnostic to RTM Alarm Output ?
Any Active Diagnostic (No)
Factory Presets: Any Active Diagnostic
Possible Values: Refer to the list of active diagnostics that can be assigned
to each GBAS output definition in the Diagnostic Menu
section on page 72.
1. Press the ENTER key, then the NEXT key to display the possible diagnostics that may
be assigned to the RTM alarm output definition.
2. Press the + (plus) key to assign yes to the output definition or - (minus) key to
assign no to the output definition.
3. Press the ENTER key to confirm each selection.
Note: Assigning “yes” to an alarm output definition means that if the assigned diagnostic
is present, the RTM alarm output will energize.
End of Submenu (NEXT) to Enter SETUP
1. Pressing the NEXT key will display the following screen.
SETUP

Other manuals for Trane IntelliPak Signature Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane IntelliPak Signature Series and is the answer not in the manual?

Trane IntelliPak Signature Series Specifications

General IconGeneral
BrandTrane
ModelIntelliPak Signature Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals