52
Programming
PKG-SVP01B-EN
(On units with a waterside economizer)
Actuator Setup Water Economizer
Min Voltage 2.0 VDC
Factory Presets: 2.0 VDC
Possible Values: 0-10 VDC
1. Pressing the NEXT key will display the following screen.
(On units with a waterside economizer)
Actuator Setup Water Economizer
Max Voltage 10.0 VDC
Factory Presets: 10.0 VDC
Possible Values: 0-10 VDC
1. Pressing the NEXT key will display the following screen.
(On units with a waterside economizer)
Actuator Setup Water Economizer
Direct/Reverse Acting Direct Acting
Factory Presets: Direct Acting
Possible Values: Direct Acting, Reverse Acting
1. Pressing the NEXT key will display the following screen.
(On units with water-cooled units)
Actuator Setup Water Econ Bypass
Max Stroke Time 150 Sec
Factory Presets: 150 Sec
Possible Values: 1-255 Sec
1. Pressing the NEXT key will display the following screen.
(On units with a waterside economizer)
Actuator Setup Water Econ Bypass
Min Voltage 2.0 VDC
Factory Presets: 2.0 VDC
Possible Values: 0-10 VDC
1. Pressing the NEXT key will display the following screen.
(On units with a waterside economizer)
Actuator Setup Water Econ Bypass
Max Voltage 10.0 VDC
Factory Presets: 10.0 VDC
Possible Values: 0-10 VDC
1. Pressing the NEXT key will display the following screen.
SETUP