RT-SVX063G-EN
117
Figure 74. Pressure curve — 40 tons eFlex variable speed
200
250
300
350
400
450
500
90 100 110 120 130 140 150 160 170 180
Suction Pressure, PSIG
Discharge Pressure, PSIG
40T eFlex Variable Speed - circuit 1 only
(Use 40T Standard Capacity for circuit 2)
95°F Ambient
85°F Ambient
75°F Ambient
65°F Ambient
105°F Ambient
Note: Full load acceptable subcooling range: 13-23°F
Figure 75. Pressure curve — 50 tons standard efficiency
200
250
300
350
400
450
500
90 100 110 120 130 140 150 160 170 180
Suction Pressure, PSIG
50T Standard Capacity
Discharge Pressure, PSIG
95°F Ambient
85°F Ambient
75°F Ambient
65°F Ambient
105°F Ambient
Note: Full load acceptable subcooling range: 13-23°F
Service and Maintenance