Figure 76. Pressure curve 50 tons high efficiency
200
250
300
350
400
450
500
90 100 110 120 130 140 150 160 170 180
Suction Pressure, PSIG
50T High Efficiency
Discharge Pressure, PSIG
95°F Ambient
85°F Ambient
75°F Ambient
65°F Ambient
105°F Ambient
Note: Full load acceptable subcooling range: 13-23°F
Figure 77. Pressure curve 50 tons eFlex variable speed
200
250
300
350
400
450
500
90 100 110 120 130 140 150 160 170 180
Suction Pressure, PSIG
50T eFlex Variable Speed - circuit 1 only
(Use 50T Standard Capacity for circuit 2)
Discharge Pressure, PSIG
95°F Ambient
85°F Ambient
75°F Ambient
65°F Ambient
105°F Ambient
Note: Full load acceptable subcooling range: 13-23°F