118
RT-SVX063G-EN
Figure 76. Pressure curve — 50 tons high efficiency
200
250
300
350
400
450
500
90 100 110 120 130 140 150 160 170 180
Suction Pressure, PSIG
50T High Efficiency
Discharge Pressure, PSIG
95°F Ambient
85°F Ambient
75°F Ambient
65°F Ambient
105°F Ambient
Note: Full load acceptable subcooling range: 13-23°F
Figure 77. Pressure curve — 50 tons eFlex variable speed
200
250
300
350
400
450
500
90 100 110 120 130 140 150 160 170 180
Suction Pressure, PSIG
50T eFlex Variable Speed - circuit 1 only
(Use 50T Standard Capacity for circuit 2)
Discharge Pressure, PSIG
95°F Ambient
85°F Ambient
75°F Ambient
65°F Ambient
105°F Ambient
Note: Full load acceptable subcooling range: 13-23°F