EasyManua.ls Logo

Trane IntelliPak with Symbio 800 - Page 120

Trane IntelliPak with Symbio 800
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
120
RT-SVX063G-EN
Figure 80. Pressure curve 55 tons eFlex variable speed
Suction Pressure, PSIG
Discharge Pressure, PSIG
200
250
300
350
400
450
500
90 100 110 120 130 140 150 160 170 180
95°F Ambient
85°F Ambient
75°F Ambient
65°F Ambient
105°F Ambient
55T eFlex Variable Speed - circuit 1 only
(Use 55T Standard Capacity for circuit 2)
Note: Full load acceptable subcooling range: 13-23°F
Figure 81. Pressure curve 60 tons standard efficiency
Suction Pressure, PSIG
Discharge Pressure, PSIG
200
250
300
350
400
450
500
90 100 110 120 130 140 150 160 170 180
60T Standard Capacity
95°F Ambient
85°F Ambient
75°F Ambient
65°F Ambient
105°F Ambient
Note: Full load acceptable subcooling range: 13-23°F
Service and Maintenance

Table of Contents

Other manuals for Trane IntelliPak with Symbio 800

Related product manuals