EasyManua.ls Logo

Trane IntelliPak with Symbio 800 - Page 121

Trane IntelliPak with Symbio 800
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RT-SVX063G-EN
121
Figure 82. Pressure curve 60 tons high efficiency
200
250
300
350
400
450
500
90 100 110 120 130 140 150 160 170 180
Suction Pressure, PSIG
60T High Efficiency
Discharge Pressure, PSIG
95°F Ambient
85°F Ambient
75°F Ambient
65°F Ambient
105°F Ambient
Note: Full load acceptable subcooling range: 13-23°F
Figure 83. Pressure curve 60 tons eFlex variable speed
200
250
300
350
400
450
500
90 100 110 120 130 140 150 160 170 180
Suction Pressure, PSIG
Discharge Pressure, PSIG
95°F Ambient
85°F Ambient
75°F Ambient
65°F Ambient
105°F Ambient
60T eFlex Variable Speed - circuit 1 only
(Use 60T Standard Capacity for circuit 2)
Note: Full load acceptable subcooling range: 13-23°F