EasyManua.ls Logo

Trane IntelliPak with Symbio 800 - Page 33

Trane IntelliPak with Symbio 800
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RT-SVX063G-EN
33
Table 4. Condenser fan electrical service sizing data (20-75 ton)
Tonnage
No. of
Motors
200 V 230 V 460 V 575 V
FLA (ea.) FLA (ea.) FLA (ea.) FLA (ea.)
20 Std 2 5.4 5.4 2.7 2.2
20 Low Ambient
1
(a)
5.6 5.6 2.9 2.4
1 5.4 5.4 2.7 2.2
25 Std 2 5.4 5.4 2.7 2.2
25 Low Ambient
1
(a)
5.6 5.6 2.9 2.4
1 5.4 5.4 2.7 2.2
30 Std 2 5.4 5.4 2.7 2.2
30 Low Ambient
1
(a)
5.6 5.6 2.9 2.4
1 5.4 5.4 2.7 2.2
40 Std 4 5.4 5.4 2.7 2.2
40 Low Ambient
2
(a)
5.6 5.6 2.9 2.4
2 5.4 5.4 2.7 2.2
50 Std 4 5.4 5.4 2.7 2.2
50 Low Ambient
2
(a)
5.6 5.6 2.9 2.4
2 5.4 5.4 2.7 2.2
55 Std 4 5.4 5.4 2.7 2.2
55 Low Ambient
2
(a)
5.6 5.6 2.9 2.4
2 5.4 5.4 2.7 2.2
60 Std 6 4.1 4.1 1.8 1.4
60 Low Ambient
2
(a)
5.6 5.6 2.9 2.4
4 4.1 4.1 1.8 1.4
70 Std 6 4.1 4.1 1.8 1.4
70 Low Ambient
2
(a)
5.6 5.6 2.9 2.4
4 4.1 4.1 1.8 1.4
75 Std 6 4.1 4.1 1.8 1.4
75 Low Ambient
2
(a)
5.6 5.6 2.9 2.4
4 4.1 4.1 1.8 1.4
(a)
Variable Speed Fan
Table 5. Electrical service sizing data —electric heat module (electric heat units only) 20 to 75 tons
Module kW
Voltage (Amps)
200 V 230 V 460 V 575 V
30 62.5 72.2 36.1 28.9
60 124.9 144.3 72.2 57.7
90 187.4 216.5 108.3 86.6
120 233.2 269.4 144.3 115.5
150 NA NA 180.4 144.3
190 NA NA 224.9 182.8
Note: Electric heat FLA are determined at 208, 240, 480 and 600 volts.
Installation

Table of Contents

Other manuals for Trane IntelliPak with Symbio 800