EasyManua.ls Logo

Trane JDAC Series - Page 21

Trane JDAC Series
86 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
21
GB
2.
MAIN
FEATURES
GB
Electrical panel situated in a compartment separated from the air ow and made in compliance with the 2006/95/CE
directive and related standards.
The table below shows the power supply available in the different possible configurations.
Power Supply 230/1/50Hz
J*AC-J*WC-J*AV-J*WV Versions
0115B
All except for units
with Enhanced Electrical Heaters
0125B
Power Supply 230/1/50Hz
J*CC-J*CV Versions
0020B
All except for units
with Enhanced Electrical Heaters
0025B
0030B
0040B
0060B Only units without Electrical heaters
Power Supply 400/3+N/50Hz
J*CC-J*CV Versions
0020A
Only units with Enhanced
Electrical Heaters
0025A
0030A
0040A
0060A
Only units with Electrical Heaters
Standard or Enhanced
Power Supply 400/3+N/50Hz
J*AC-J*WC-J*AV-J*WV Versions
0115A
All
0125A
0133A
0135A
0150A
0160A
The main features are as follows:
฀฀฀฀฀฀฀฀฀฀฀
฀฀฀฀฀฀฀
฀฀฀฀฀฀
฀฀฀฀฀฀฀฀฀฀
All of the units undergo a safety test cycle to check the continuity of the protection circuit and the insulation resistance
and a voltage test (dielectric strength).
Power factor condensers are available for all Direct Expansion Models with 400/3+N/50Hz.
LIMITS
Min Max
hydrogen-ion activity pH 7 8,5
฀฀฀
σR฀
μS/cm 350 1250
total solid dissolved TDS mg/l (¹) (¹)
฀฀฀R
180 mg/l (¹) (¹)
total hardness TH mg/l CaCO
3 100 (²) 400
temporary hardness mg/l CaCO
3 60 (³) 300
iron + Manganese mg/l Fe + Mn 0 0,2
chlorides ppm Cl 0 30
silica mg/l SiO
2 0 20
residual chlorine mg/l CҐ 0 0,2
calcium sulphate mg/l CaSO
4 0 100
metallic impurities mg/l 0 0
solvents, diluents, soaps, lubricants mg/l 0 0
(¹) Values depend on the specific conductivity; in general: TDS = 0,93*
σ
20; R180 = 0,65*σ20
฀฀฀฀฀฀฀฀฀฀฀฀Ґ
฀฀฀฀฀฀฀฀฀฀฀฀Ґ
LIMIT VALUES FOR THE SUPPLY WATER WITHIN AN IMMERSED ELECTRODE HUMIDIFIER
Immersed-electrode humidifier for modulating sterile steam production with automatic regulation of the concentration
of salts in the boiler to allow for the use of untreated water. It is therefore possible to use water with varying degrees of
hardness and without the need for any chemical treatment or demineralising. The humidifier has a steam cylinder, a steam
distributor (installed immediately downstream from the exchanger), water intake and delivery valves and a maximum
level sensor. Proportional control of the humidier operation (achieved by controlling the electric current allowed to
pass through the cylinder’s electrodes and the management of salt concentration inside the cylinder) guarantee perfect
efficiency of the system, energy saving and greater durability of the components.
The steam cylinder is installed outside the air flow to avoid any heat losses. The unit’s microprocessor control indicates
when the steam cylinder has to be changed because it is empty; the steam cylinder can be, on request, the type which
is able to be inspected so that the electrodes can be routinely cleaned to remove any lime scale. The maximum steam
capacity production is adjustable within a range of values between 2 and 3 kg/h which can be selected manually.

Related product manuals