General Information
RTHD-SVX01K-EN 13
3-pass
Connection size
in 8 8 8 8 10 10 8 8
mm 200 200 200 200 250 250 200 200
Min Flow -
Water(d)
gpm 234 404 275 376 505 550 300 404
l/s1525172435351925
Maximum Flow
gpm 1028 1780 1206 1655 2218 2413 1320 1780
l/s 65 112 76 104 140 152 83 112
4-pass
Connection size
in - - - - 8 8 - -
mm - - - - 200 200 - -
Min Flow -
Water(d)
gpm - - - - 379 411 - -
l/s - - - - 24 26 - -
Maximum Flow
gpm - - - - 1666 1807 - -
l/s - - - 105 114 - -
CONDENSER (all are 2-pass)
Connection size
in88888888
mm 200 200 200 200 200 200 200 200
Water Storage
gal3261445779914761
L 121 231 166 216 299 344 178 231
Min Flow -
Water(d)
gpm 245 355 291 355 444 535 316 385
l/s1522182228342024
Max Flow
gpm 1080 1700 1280 1560 1960 2360 1390 1700
l/s 68 107 81 98 124 149 88 107
(a) Unit configuration digits 1, 2 - compressor code (also shown in unit model number digits 6, 7); digits 3, 4 - evaporator code (unit model number digits
14, 15); digits 5, 6 - condenser code (unit model number digits 21, 22).
(b)See model number digit 35 for refrigerant type, and digit 39 for starter type.
(c) If oil cooler is installed (model number digit 30 = C), add 0.3 gal (1L) to oil charge value given for B compressor family units. Add 1.0 gal (4L) for all
other units.
(d)See unit submittal or Trane Select Assist (TSA) report for design/selected minimum flows.
Table 2. General data (continued)
Description Units
Unit Configuration
(a)
C2D4E4 C2F2F3 D1D1E1 D1F1F2 D1G1G1 D1G2G2 D2D2E2 D2F2F3
Table 3. General data
Description Units
Unit Configuration
(a)
D2G2G1 D2G3G3 D3D2E2 D3F2F3 D3G2G1 E3D2E2 E3F2F3 E3G2G1 E3G3G3
GENERAL
Refrigerant Type R-134a or R-513A R-134a
Refrigerant
Charge
lb 700 700 475 625 700 475 625 700 700
kg 318 318 216 284 318 216 284 318 318
Wye-delta starter
with R-134a
(b)
Oil Type OIL48
Oil Charge
(c)
gal 11 11 6 10
11
6101111
L 42 4223384223384242