BAS-SVX078E-EN
37
only occur on peak energy demand days. The Pivot thermostat now has OADR screens which allows it
to participate in these events if the user chooses.
To register your thermostat in the Demand Response program, navigate to Home > Menu > System
Info > Demand Response > Registration.
The URL and Port Number will be from the utility or aggregator website. The VEN ID is an identity you
create for your thermostat.
Recovery
The Pivot thermostat uses a stage inhibit to limit equipment staging. The stage inhibit can be disabled
by two methods:
Aggressive recovery disables stage inhibits in heating/cooling mode anytime the setpoint is adjusted
more than 2°F.
Heating aggressive recovery disables stage inhibits in only heating mode when the outdoor
temperature falls below the selected outdoor temperature.
Ventilation Operation
The Pivot thermostat is capable of controlling a ventilation system through a configurable dry AUX
contact on the unit sub-base. All ventilation operation control options are accessed by navigating to
Installer Setup > Accessories Settings. Refer to figure 5, “Reliatel constant volume with non-variable
speed blower and occupancy signal” in the Wiring Diagrams section for a wiring example.
Ventilation only runs during scheduled occupied periods.
The blower can be configured for interlocked on a call for ventilation (Ventilator Fan Action).
The ventilation runtime per hour can be adjusted to meet ASHRAE 62 standards for acceptable
indoor air quality by setting up Minimum Ventilation Runtime.
Temperature override can be set to prevent ventilation operation when the outdoor temperature
exceeds the minimum or maximum outdoor temperature settings. (Ventilation Minimum Outdoor
Air Temperature and Ventilation - Maximum Outdoor Air Temperature).
Missed Ventilation Runtime. A selection can be made to accumulate the missed ventilation runtime.
The following ventilation accumulate options will only be displayed as a choice in the Installer Setup
when all of the following four options are set up as described:
Use Internet Weather is set to Yes, and/or ODT Input is configured for outdoor air temperature
sensor (Installer Setup > Sensor Settings).
A valid postal code must be configured in the weather settings if using Internet Weather for
outdoor air temperature (Home > Menu > Settings > Weather).
Outdoor Air Temperature Ventilation Override is enabled (Installer Setup > Accessories
Settings).
Accumulate Overridden Run Time is Yes (Installer Setup > Accessories Settings).
Ventilation accumulate options (Installer Setup > Accessories Settings > Accumulate Period):
Accumulate missed ventilation runtime in 4–hour increments and make up when the outdoor
temperature is within the min/max settings.
Accumulate missed ventilation runtime in 24–hour increments and make up when the outdoor
temperature is within the min/max settings.
Accumulate missed ventilation runtime in 4–hour increments and make up at the end of the 4–hour
period.
Accumulate missed ventilation runtime in 24–hour increments and make up at the end of the 24–
hour period.
Occupancy Signal
If the thermostat is running a schedule and an occupancy output signal is necessary, follow these steps
using Installer > Setup > Accessories Settings.
Advanced Operation

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Pivot BAYSTAT814 Series and is the answer not in the manual?

Trane Pivot BAYSTAT814 Series Specifications

General IconGeneral
BrandTrane
ModelPivot BAYSTAT814 Series
CategoryThermostat
LanguageEnglish

Related product manuals