CG-SVX039C-GB
CXAF CXAF CXAF CXAF CXAF CXAF
130 140 150 165 180 190
HE HE HE HE HE HE
Single pump - High head pressure option
Max available Head Pressure (kPa) 232 252 258 249 230 221
Motor Power (kW) 11.0 15.0 15.0 15.0 15.0 15.0
Rated Amps (A) 20.8 28.0 28.0 28.0 28.0 28.0
Twin pump - Standard head pressure option
Max available Head Pressure (kPa) 157 141 143 182 163 154
Motor Power (kW) 7.5 7.5 7.5 11.0 11.0 11.0
Rated Amps (A) 14.4 14.4 14.4 20.8 20.8 20.8
Twin pump - High head pressure option
Max available Head Pressure (kPa) 232 252 258 249 230 221
Motor Power (kW) 11 15 15 15 15 15
Rated Amps (A) 20.8 28 28 28 28 28
Expansion Tank Volume (l) 50 50 50 50 50 50
Max User water loop Volume for factory
mounted expansion tank (1)
(l) 1750 1750 1750 1750 1750 1750
Optional water Buffer tank volume (l) 607 777 777 777 777 777
Antifreeze Heater without pump package
and without buffer tank
(W) 520 640 640 640 640 640
Antifreeze Heater with pump package and
without buffer tank (Single Water Pump digit 24=2
or 4 / Dual Water Pump digit 24=1 or 3)
(W) 1060/1120 1340/1400 1340/1400 1340/1400 1340/1400 1340/1400
Antifreeze Heater with pump package and
with buffer tank (Single Water Pump digit 24=2 or 4
/ Dual Water Pump digit 24=1 or 3)
(W) 2040/2100 2790/2850 2790/2850 2790/2850 2790/2850 2790/2850
Antifreeze Heater with pump package and with buffer
tank (Single Water Pump digit 24=2 or 4 / Dual
Water Pump digit 24=1 or 3)
(W)
1940/
2000
1940/
2000
1940/
2000
2040/
2100
2040/
2100
2790/
2850
Condenser
Type Fin-tube heat exchanger
Quantity of coil # 8 10 10 10 12 12
Face area per circuit (m²) 9.29 11.61 11.61 11.61 13.93 13.93
Condenser Fan
Quantity # 8 10 10 10 12 12
Diameter (mm) 800
Digit 56=1
Fan / motor Type Fixed speed AC motor
Airow per fan m3/h 17984 18055 18019 17976 18028 17990
Max Power Input per Motor Kw 1.13 1.13 1.13 1.13 1.13 1.13
Max Amps per Motor A 2.2 2.2 2.2 2.2 2.2 2.2
Motor RPM (rpm) 900 900 900 900 900 900
Digit 56=2
Fan / motor Type
Variable speed EC motor
Airow per fan m3/h 18992 17571 18388 18984 17970 18999
Max Power Input per Motor Kw 1.55 1.55 1.55 1.55 1.55 1.55
Max Amps per Motor A 2.5 2.5 2.5 2.5 2.5 2.5
Motor RPM (rpm) 950 880 920 950 900 950
Digit 56=3
Fan / motor Type
Variable speed EC motor with Axitop
Airow per fan m3/h 19210 17877 18543 19201 18317 19216
Max Power Input per Motor Kw 1.82 1.82 1.82 1.82 1.82 1.82
Max Amps per Motor A 2.9 2.9 2.9 2.9 2.9 2.9
Motor RPM (rpm) 880 820 850 880 840 880
Dimensions
Unit Length (mm) 4520 5645 5645 5645 6770 6770
Unit Width (mm) 2200 2200 2200 2200 2200 2200
Std Unit Height (mm) 2526 2526 2526 2526 2526 2526
Pump Package Option - (Additional length
conguration)
(mm) 562 562 562 562 562 562
Weights (6)
Shipping Weight (6) (kg) 3201 3848 4024 4064 4523 4592
Table 8 – General data CXAF 130-190 High Efficiency (continued)
General Data