CXAF CXAF CXAF CXAF CXAF CXAF
130 140 150 165 180 190
HE HE HE HE HE HE
Option Additional shipping weight (6)
Single pump - Standard head pressure (kg) 264 287 287 351 401 401
Single pump - High head pressure (kg) 301 363 363 363 413 413
Twin pump - Standard head pressure (kg) 363 386 386 495 545 545
Twin pump - High head pressure (kg) 425 521 521 521 571 571
XLN option (kg) 114 145 145 145 145 145
Pump VFD option (kg) 70 70 70 70 70 70
Water Buffer tank option (kg) 286 379 379 379 379 379
System data
Nb of refrigerant circuit # 2 2 2 2 2 2
Minimum cooling load % (6) % 25 15 17 15 14 17
Total number of capacity steps # 4 14 6 14 14 6
Standard/Partial Heat Recovery Unit
R410A refrigerant charge Circuit 1 / Circuit 2 (kg) 50 / 50 67 / 70 68 / 71 68 / 71 77 / 80 78 / 81
Oil charge Circuit 1 / Circuit 2 (l) 17.4 / 17.4 25.4/25.4 25.6/25.6 25.5/25.5 26.3/26.3 26.3/26.3
POE Oil type OIL058E / OIL057E
(1) Indicative performance at Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C for cooling & Condenser water temperature:
40°C / 45°C - Evaporator air temperature 7°C (6°C) - for detailed performances, on a given unit, consult Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(5) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch.
(6) For detail information refer submittal drawing which are available in the unit.