EasyManua.ls Logo

Trane SINTESIS ADVANTAGE CXAF Series - Option Free-Cooling

Trane SINTESIS ADVANTAGE CXAF Series
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
68
CG-SVX039C-GB
Option Free-Cooling
Figure 25 – Free-Cooling Operating Maps
-25
-20
-15
-10
-5
0
5
10
15
20
25
-15-10 -5 0510 15 20 25 30
Ambient Temperature / C
Customer Entering Temperature / C
Glycol Free Free Cooling Operaon M ap
EC FAN
AC FAN
-25
-20
-15
-10
-5
0
5
10
15
20
25
-15-10 -5 0510 15 20 25 30
Ambient Temperature / C
Customer Entering Temperature / C
Direct Free Cooling Operation Map
EC FAN
AC FAN
Figure 26 – Free-Cooling Water pressure drop
The free-cooling water pressure drops given in charts below (coil + valve) should be added to evaporator pressure
drop to get full unit pressure drop.
5
10
20
40
80
160
320
4 8 16 32 64
Pressure Drop (kPa)
Water Flow Rates (L/s)
Glycol Free - Free Cooling (CGAF SE/HE/XE)
1- SE-90/100/110/130
HE/XE-80
2- SE-140/150/165
HE/XE-90/100/110/130
3- SE-180/190
HE/XE-140/150/165
4- HE/XE-180/190
1
2
3
4
5
10
20
40
80
160
4 8 16 32 64
Pressure Drop (kPa)
Water Flow Rates (L/s)
Direct Free Cooling - CGAF SE/HE/XE
1 - SE-90/100/110/130
HE/XE-80
2 - HE-90/100/110/130
3- SE-140/150/165
4 - SE-180/190
HE/XE-140/150/165
5 - HE/XE-180/190
2
3
1
4
5
2
3
1
4
5