11UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08 2 57 54 47 40 30 38 40 50
3 58 57 50 42 32 40 43 53
1 57 51 45 42 34 33 28 48
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 62 60 60 53 53 53 64
3 66 65 63 62 56 55 57 67
1 62 58 55 58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
FWD 12 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
3 78 79 71 74 69 66 66 78
CG-SVX051A-GB
15
Unit size 080 090 100 110 130
Digit 56=2 EC fan
Max Power Input per Motor kW N/A N/A N/A N/A N/A
Max Amps per Motor A N/A N/A N/A N/A N/A
Motor RPM (Cooling mode) rpm/min N/A N/A N/A N/A N/A
Digit 56=3 EC fan HESP
Max Power Input per Motor kW N/A N/A N/A N/A N/A
Max Amps per Motor A N/A N/A N/A N/A N/A
Motor RPM (Cooling mode eld setting) rpm/min N/A N/A N/A N/A N/A
Chilled Water Pump Package options
Single pump - Standard head pressure (digit 24=2)
Available Head Pressure (1) kPa 125 126 112 157 151
Motor Power kW 5.5 5.5 5.5 7.5 7.5
Rated Amps A 11.0 11.0 11.0 14.4 14.4
Single pump - High head pressure (digit 24=4)
Available Head Pressure (1) kPa 250 254 243 233 228
Motor Power kW 11.0 11.0 11.0 11.0 11.0
Rated Amps A 20.8 20.8 20.8 20.8 20.8
Dual pump - Standard head pressure (digit 24=1)
Available Head Pressure (1) kPa 125 126 112 157 151
Motor Power kW 5.5 5.5 5.5 7.5 7.5
Rated Amps A 11.0 11.0 11.0 14.4 14.4
Dual pump - High head pressure (digit 24=3)
Available Head Pressure (1) kPa 250 254 243 233 228
Motor Power kW 11.0 11.0 11.0 11.0 11.0
Rated Amps A 20.8 20.8 20.8 20.8 20.8
Optional Expansion Tank Volume l 50 50 50 50 50
Max User water loop Volume for factory- mounted
expansion tank (1)
l 1750 1750 1750 1750 1750
Optional water Buffer tank volume l 607 607 607 607 607
Hot Water Pump Package Options
Single pump - Standard head pressure (digit 59=2)
Available Head Pressure (1) kPa 190 189 181 174 166
Motor Power kW 3.0 3.0 3.0 3.0 3.0
Rated Amps A 5.9 5.9 5.9 5.9 5.9
Single pump - High head pressure (digit 59=4)
Available Head Pressure (1) kPa 321 321 313 306 297
Motor Power kW 5.5 5.5 5.5 5.5 5.5
Rated Amps A 10.5 10.5 10.5 10.5 10.5
Dual pump- Alternate running - Standard head pressure (digit 59=1)
Available Head Pressure (1) kPa 189 186 178 170 162
Motor Power kW 3.0 3.0 3.0 3.0 3.0
Rated Amps A 5.9 5.9 5.9 5.9 5.9
Dual pump - Alternate running - High head pressure (digit 59=3)
Available Head Pressure (1) kPa 321 317 341 301 293
Motor Power kW 5.5 5.5 5.5 5.5 5.5
Rated Amps A 10.5 10.5 10.5 10.5 10.5
Dual pump - Simultaneous running - Standard head pressure (digit 59=5)
Available Head Pressure (5) kPa 159 157 143 135 127
Motor Power kW 6.0 6.0 6.0 6.0 6.0
Rated Amps A 11.8 11.8 11.8 11.8 11.8
Dual pump - Simultaneous running - High head pressure(digit 59=6)
Available Head Pressure (5) kPa 290 289 274 267 257
Motor Power kW 11.0 11.0 11.0 11.0 11.0
Rated Amps A 21.0 21.0 21.0 21.0 21.0
Antifreeze protection option
Without any Water Pump Package
"Without chilled water and hot water pump
package (digit 24=X and digit 59=X)"
kW
0.66 0.72 0.72 0.82 0.92
Combinations without Hot Water Pump Package
With chilled water single pump and without
hot water pump package without buffer tank
(digit 24=2/4, digit 50=X digit 59=X)
kW 1.30 1.36 1.36 1.46 1.56
With chilled water dual and without hot water
pump package without buffer tank (digit
24=1/3, digit 50=X digit 59=X)
kW 1.36 1.42 1.42 1.5 1.6
With chilled water single pump and without hot
water pump package with buffer tank (digit
24=2/4, digit 50≠X digit 59=X)
kW 2.18 2.24 2.24 2.34 2.44
With chilled water dual pump and without hot
water pump package with buffer tank (digit
24=1/3, digit 50≠X, digit 59=X)
kW 2.24 2.30 2.30 2.40 2.50
Table 2 - General data CMAF 080-130 Standard Efficiency (Continued)