4 UNT-PRC002-GB
Technical Data
FWD 08 12 20 30 45
Power supply (V/Ph/Hz) 230/1/50
Capacities
Cooling capacity on water (1) (kW) 5,2 8,3 15 18,8 30,1
Heating capacity on water (2) (kW) 6,3 11,9 18,9 20,9 38,2
Fan motor (type) 2 x direct drive centrifugal
Fan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51
Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5
Start-up amps (A) 3,2 5,5 9,3 14,1 16,5
Air flow
minimum (m
3
/h) 490 980 1400 1800 2700
nominal (m
3
/h) 820 1650 2300 3000 4500
maximum (m
3
/h) 980 1970 2600 3600 5400
Main coil
Water entering/leaving connections (type) ISO R7 rotating female
(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"
Electric heater (accessory for blower only)
Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50
Heating capacity (kW) 2/4 8 10 12 12
Hot water coil (accessory for blower only)
Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5
G2 filter (filter box accessory)
Quantity 2 2 2 2 2
Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8
G4 filter (filter box accessory)
Quantity - 2 2 2 2
Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48
Condensate pump (accessory) (type) Centrifugal
Water flow - lift height (l/h - mm) 24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58
Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68
Unit dimensions
Width x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090
Height (mm) 250 300 350 450 650
Shipped unit dimensions
Width x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133
Height (mm) 260 310 360 460 660
Weight (kg) 32 46 61 76 118
Colour galvanised steel
Recommended fuse size
Unit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25
Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
CG-SVX051A-GB
18
Unit size 140 150 165 180 190
Digit 56=2 EC fan
Max Power Input per Motor kW N/A N/A N/A N/A N/A
Max Amps per Motor A N/A N/A N/A N/A N/A
Motor RPM (Cooling mode) rpm/min N/A N/A N/A N/A N/A
Digit 56=3 EC fan HESP
Max Power Input per Motor kW N/A N/A N/A N/A N/A
Max Amps per Motor A N/A N/A N/A N/A N/A
Motor RPM (Cooling mode eld setting) rpm/min N/A N/A N/A N/A N/A
Chilled Water Pump Package options
Single pump - Standard head pressure (digit 24=2)
Available Head Pressure (1) kPa 131 134 122 155 161
Motor Power kW 7.5 7.5 11.0 11.0 11.0
Rated Amps A 14.4 14.4 20.8 20.8 20.8
Single pump - High head pressure (digit 24=4)
Available Head Pressure (1) kPa 240 248 243 224 231
Motor Power kW 15.0 15.0 15.0 15.0 15.0
Rated Amps A 28.0 28.0 28.0 28.0 28.0
Dual pump - Standard head pressure (digit 24=1)
Available Head Pressure (1) kPa 131 134 122 155 161
Motor Power kW 7.5 7.5 11.0 11.0 11.0
Rated Amps A 14.4 14.4 20.8 20.8 20.8
Dual pump - High head pressure (digit 24=3)
Available Head Pressure (1) kPa 240 248 243 224 231
Motor Power kW 15.0 15.0 15.0 15.0 15.0
Rated Amps A 28.0 28.0 28.0 28.0 28.0
Optional Expansion Tank Volume l 50 50 50 50 50
Max User water loop Volume for factory- mounted
expansion tank (1)
l 1750 1750 1750 1750 1750
Optional water Buffer tank volume l 777 777 777 777 777
Hot Water Pump Package Options
Single pump - Standard head pressure (digit 59=2)
Available Head Pressure (1) kPa 197 196 193 189 181
Motor Power kW 5.5 5.5 5.5 5.5 5.5
Rated Amps A 10.5 10.5 10.5 10.5 10.5
Single pump - High head pressure (digit 59=4)
Available Head Pressure (1) kPa 290 288 284 273 267
Motor Power kW 7.5 7.5 7.5 7.5 7.5
Rated Amps A 13.9 13.9 13.9 13.9 13.9
Dual pump- Alternate running - Standard head pressure (digit 59=1)
Available Head Pressure (1) kPa 191 189 187 177 173
Motor Power kW 5.5 5.5 5.5 5.5 5.5
Rated Amps A 10.5 10.5 10.5 10.5 10.5
Dual pump - Alternate running - High head pressure (digit 59=3)
Available Head Pressure (1) kPa 285 282 277 265 258
Motor Power kW 7.5 7.5 7.5 7.5 7.5
Rated Amps A 13.9 13.9 13.9 13.9 13.9
Dual pump - Simultaneous running - Standard head pressure (digit 59=5)
Available Head Pressure (5) kPa 145 144 139 119 107
Motor Power kW 11.0 11.0 11.0 11.0 11.0
Rated Amps A 21.0 21.0 21.0 21.0 21.0
Dual pump - Simultaneous running - High head pressure(digit 59=6)
Available Head Pressure (5) kPa 239 236 230 207 197
Motor Power kW 15.0 15.0 15.0 15.0 15.0
Rated Amps A 27.8 27.8 27.8 27.8 27.8
Antifreeze protection option
Without any Water Pump Package
"Without chilled water and hot water pump
package (digit 24=X and digit 59=X)"
kW
1.04 1.04 1.04 1.04 1.04
Combinations without Hot Water Pump Package
With chilled water single pump and without
hot water pump package without buffer tank
(digit 24=2/4, digit 50=X digit 59=X)
kW 1.74 1.74 1.74 1.74 1.74
With chilled water dual and without hot water
pump package without buffer tank (digit
24=1/3, digit 50=X digit 59=X)
kW 1.80 1.80 1.80 1.80 1.80
With chilled water single pump and without hot
water pump package with buffer tank (digit
24=2/4, digit 50≠X digit 59=X)
kW 3.19 3.19 3.19 3.19 3.19
With chilled water dual pump and without hot
water pump package with buffer tank (digit
24=1/3, digit 50≠X, digit 59=X)
kW 3.25 3.25 3.25 3.25 3.25
Table 3 - General data CMAF 140-190 Standard Efficiency (Continued)
General Data