11UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08 2 57 54 47 40 30 38 40 50
3 58 57 50 42 32 40 43 53
1 57 51 45 42 34 33 28 48
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 62 60 60 53 53 53 64
3 66 65 63 62 56 55 57 67
1 62 58 55 58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
FWD 12 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
3 78 79 71 74 69 66 66 78
CG-SVX051A-GB
7
Digit 1, 2, 3, 4 – Unit Model
CMAF = Air-to-water Multi-pipe Scroll Unit
Digit 5-7 – Unit Nominal Tonnage
080 = 80 Tons
090 = 90 Tons
100 = 100 Tons
110 = 110 Tons
130 = 130 Tons
140 = 140 Tons
150 = 150 Tons
165 = 165 Tons
180 = 180 Tons
190 = 190 Tons
Digit 8 – Unit voltage
D = 400V/50Hz/3ph
G = 400V/50Hz/3ph Compatible with IT Neutral
Digit 9 – Manufacturing Location
E = Europe, TRANE Unit
F = Europe, ICS Unit
Digit 10, 11 – Design sequence
** = Factory assigned
Digit 12 – Efficiency
U = Standard Efficiency Short
N = Standard Efficiency
H = High Efficiency
Digit 13 – Agency listing
C = CE Certification (Europe)
Digit 14 – Pressure vessel code
2 = PED (Pressure equipment directive)
Digit 15 – Acoustic level
X = Standard noise (SN)
L = Low noise (LN)
E = Extra Low Noise (XLN)
Digit 16 – Unit Application
L = Low ambient air temperatures: Cooling mode -
20°C(EC Fans) or -10°C (AC Fans) /+50°C ; Heating mode
-18°C/+20°C (AC Fans) or +35°C (EC Fans)
Digit 17 – Relief valve option
W = Without
Digit 18 – Water connection
X = Standard Grooved pipe connection
W = Grooved pipe + welded coupling
2 = Grooved pipe with coupling and Flange adapter
Digit 19 – Evaporator Application
N = Standard cooling [-2°C up to + 20°C ]
Digit 20 – Evaporator Configurations
B = Brazed plate heat exchanger
Digit 21 – Thermal Insulation
N = Standard thermal insulation
Digit 22 – Condenser Coating
B = Hydrophilic (blue) Coated Fin
E = Epoxy Coated Aluminum Fin
Digit 23 – Heat Recovery
X = No Heat Recovery
Digit 24 – Hydraulic module
X = Pump signal On/Off
1 = Dual pump standard pressure
2 = Single pump standard pressure
3 = Dual pump high pressure
4 = Single pump high pressure
Digit 25 – Free Cooling
X = No Free Cooling
Digit 26 – Power line type connection
B = Disconnect switch
Digit 27 – Control Panel Accessories
X = None
1 = Under/Over Voltage Protection
2 = Under/Over Voltage Protection with ground fault protection
Digit 28 – Human Interface language
C = Spanish
D = German
E = English
F = French
H = Dutch
I = Italian
M = Swedish
P = Polish
R = Russian
T = Czech
U = Greek
V = Portuguese
2 = Romanian
6 = Hungarian
8 = Turkish
Digit 29 – Smart com protocol
X = None
B = BACnet MS/TP interface
M = Modbus RTU interface
C = BACnet TCP/IP interface
N = ModBus TCP Interface
Digit 30 – External Control Package
X = None
A = External set point & auxiliary setpoint and External
Operating mode priority
Digit 31 – Flow switch
1 = Factory installed electronic flow switch
Digit 32 – Electrical Panel Protection
X = Enclosure with deadfront protection
1 = Enclosure with IP 20 internal protection
Digit 33 – Master Slave
X = Without
A = With
Digit 34 – Human Interface
L = Standard, Local UI supplied
Digit 35 – Energy meter
X = No energy meter
M = Energy meter installed
Digit 36 – Mini Multi-Pipe Unit Plant Control
X = No Mini PC
Digit 37 – Chilled Loop Primary Flow Control
X = Constant speed pump (no VFD)
F = With VFD for manual flow adjustment
Digit 38 – Refrigerant Loss alarm
X = Not installed
V = Installed
Digit 39 – Web server
X = Not installed
Digit 40 – Power socket
X = None
P = Included (230V - 100W)
Unit model number description