11UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08 2 57 54 47 40 30 38 40 50
3 58 57 50 42 32 40 43 53
1 57 51 45 42 34 33 28 48
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 62 60 60 53 53 53 64
3 66 65 63 62 56 55 57 67
1 62 58 55 58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
FWD 12 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
3 78 79 71 74 69 66 66 78
CG-SVX051A-GB
19
Unit size 140 150 165 180 190
Combinations with Hot water Package
Without chilled water pump and with hot water
pump single or dual package without buffer
tank (digit 24=X, digit 50=X, digit 59≠X)
kW 1.54 1.54 1.54 1.54 1.54
With chilled water single pump and with hot
water pump single or dual package without
buffer tank (digit 24=1/3, digit 50=X,
digit 59≠X)
kW 2.24 2.24 2.24 2.24 2.24
With chilled water dual pump and with hot
water pump single or dual package without
buffer tank (digit 24=2/4, digit 50=X,
digit 59≠X)
kW 2.30 2.30 2.30 2.30 2.30
With chilled water single pump and with hot
water pump single or dual package without
buffer tank (digit 24=1/3, digit 50≠X,
digit 59≠X)
kW 3.69 3.69 3.69 3.69 3.69
With chilled water dual pump and with hot
water pump single or dual package with buffer
tank (digit 24=2/4, digit 50≠X, digit 59≠X)
kW 3.75 3.75 3.75 3.75 3.75
Dimensions and weight (basic model only)
Length mm 5645 5645 5645 6770 6770
Width mm 2200 2200 2200 2200 2200
Height mm 2530 2530 2530 2530 2530
Pump Package Option - (Additional length) mm 555 555 555 555 555
Weights
Operating Weight kg 3753 3956 4056 4458 4559
Additional Shipping Weight kg 18 18 18 24 24
Additional Weight of options
Chilled water pump
Single pump - Standard head pressure kg 287 287 351 401 401
Single pump - High head pressure kg 363 363 363 413 413
Twin pump - Standard head pressure kg 386 386 495 545 545
Twin pump - High head pressure kg 521 521 521 571 571
Hot water pump
Single pump - Standard head pressure kg 208 208 208 208 208
Single pump - High head pressure kg 193 193 193 193 193
Double pump - Standard head pressure kg 312 312 312 312 312
Double pump - High head pressure kg 335 335 335 335 335
Extra Low Noise (XLN) Option kg 145 145 145 145 145
Optional Pump VFD kg 85 85 85 85 85
Optional Chilled Water Buffer tank kg 333 333 332 332 332
Oil and Refrigerant Charge (R410A)
Total Refrigerant charge Circuit 1/2 (6) kg 59/60 59/60 60/61 69/68 69/69
Refrigerant Charge per cooling kW (6) kg/kW 0.25 0.24 0.22 0.23 0.22
POE Oil Type OIL058E / OIL057E
Oil charge Circuit 1 / 2 (6) l 23.5 / 23.5 23.6 / 23.6 23.5 / 23.5 23.4 / 23.4 23.4 / 23.4
(1) Indicative performance at chilled water exchanger water temperature : 12˚C / 7˚C and air temperature 35˚C for cooling only mode & hot water
exchanger temperature: 40˚C / 45˚C and air temperature 7˚C (6˚C) for heating only mode for- detailed performances, on a given unit, consult Order
Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(5) Hot water exchanger temperature 40˚C / 50 ˚C and air temperature 7˚C (6˚C) for heating only mode.
(6) Refrigerant and oil charges are indicative. Refer to unit nameplate for real charges.
Table 3 - General data CMAF 140-190 Standard Efficiency (Continued)
General Data