PKG-SVX029A-EN
27
convention of connecting zone sensor terminals to like
numbered unit terminals (1 to 1, 2 to 2).The connection
detail is shown on the unit wiring diagrams located in
the unit control panel.
3. Replace the zone sensor cover back on the subbase
and snap securely into place.
Standard Remote Sensor (BAYSENS077)
When using the remote sensor, BAYSENS077, mount it in
the space that is to be controlled. Wire according to the
interconnecting wiring diagrams on the unit.
Table 9. Zone sensor maximum lengths and wire size
Distance from Unit to
Controller
Recommended Wiring Size
0-150 feet 22 gauge
151-240 feet 20 gauge
241-385 feet 18 gauge
386-610 feet 16 gauge
611-970 feet 14 gauge
Figure 14. Typical zone sensor installation
Installation - Electrical