PKG-SVX029A-EN
17
Service Clearances
Figure 5. Service clearance
Left Side
42"
Right Side
24"
Back - Air Inlet
18"
Front
42"
1) Low Voltage
(Control Panel)
2) High Voltage
Starter Control
Electrical conduit penetrations
(recommended)
Table 5. Service/code clearance requirements
Side
Distance - in. (mm) Purpose
Front 42
NEC Code Requirements; Fan, Compressor, Condenser, Service/Removal
Left 42
NEC Code Requirements
Right
24 Door Clearance
Back 18 Provides Uniform Airflow
Dimensional Data