BAS-SVX084A-EN 15
Wiring Installation
Replace the control box cover after field wiring to prevent any electromagnetic interference.
•Review Table 7 for factory-installed components and voltage amperage.
Table 6. Binary load values
Below is an example VA draw calculation for a BACnet MS/TP controller on a cooling-only VAV box:
Description Draw
•Symbio no I/O
Setpoint and Zone Temperature Sensor Input
Air Flow Sensor Input
Occupancy Input
Binary Out for Air Damper (only one energized at a time, not
including actuator draw)
Trane F Series Air Damper Actuator (Taken from Table 7, p. 16)
Total
•8.0 VA
•0 VA
•0.3 VA
•0.1 VA
•0.1 VA
•4.0 VA
12.5 VA
Below is an example VA draw calculation for a BACnet IP controller on a hot water reheat VAV box:
Description Draw
Symbio 210e
Setpoint and Zone Temperature Sensor Input
Air Flow Sensor Input
Binary Out for Water Valve (only one energized at a time, not
including actuator draw)
Belimo Hot Water Actuator (TR24-3)
Binary Out for Air Damper (only one energized at a time, not
including actuator draw)
Trane F Series Air Damper Actuator (Taken from Table 7, p. 16)
Total
•9.5 VA
•0 VA
•0.3 VA
•0.1 VA
•1.0 VA
•0.1 VA
•4.0 VA
15 VA
Below is an example VA draw calculation for a BACnet Zigbee controller with XM on a hot water reheat VAV box:
Description Draw
Symbio 210
Air-Fi WCI (X13790901030)
(c)
Air Flow Sensor Input
•XM32
Binary Out for Water Valve (only one energized at a time, not
including actuator draw)
Belimo Hot Water Actuator (TR24-3)
Binary Out for Air Damper (only one energized at a time, not
including actuator draw)
Trane F Series Air Damper Actuator (Taken from Table 7, p. 16)
Total
•8.0 VA
0.5 VA (10 mA WCI power draw)
•0.3 VA
5.0 VA (100 mA XM32 power draw)
•0.1 VA
•1.0 VA
•0.1 VA
•4.0 VA
19 VA
(a)Insignificant load.
(b)See device connected to DC supply for current draw.
(c) Older WCI version draw more current than current design.
Table 5. Calculating actual VA requirements (continued)
Item Sub VA Draw Per I/O (24 Vac)
Maximum Total VA Draw (24
Vac)
Style Volt Amps
F - Style Actuator 4 VA
Air Valve Actuator C through E Style 12 VA
Fan Power Fan Output 6 VA
Hot Water Proportional 4 VA
Hot Water 2 Position 6.5 VA
Electric Heater Magnetic Contactor 10 VA
Electric Heater Mercury Contactor 12 VA