Wiring Installation
Wiring Best Practices
To ensure proper network communication, follow the recommended wiring and best practices
below when installing communication wire:
All wiring must comply with the National Electrical Code™ (NEC) and local codes.
Ensure that 24 Vac power supplies are consistent in regards to grounding. Avoid sharing 24 Vac
between controllers.
Avoid over tightening cable ties and other forms of cable wraps. This can damage the wires
inside the cable.
Do not run communication cable alongside or in the same conduit as 24 Vac power. This
includes the conductors running from TRIAC-type inputs.
In open plenums, avoid running wire near lighting ballasts, especially those using 277 Vac.
Use same communication wire type, without terminators, for the zone sensor communication
stubs from the Symbio 210 controller IMC terminals to the zone sensor communication module.
Zone Sensor communication wiring length limits of 300 ft. (100 m).
Note: For more details, refer to the BACnet Best Practices and Troubleshooting Guide
(BAS-SVX51-EN).
Figure 4. BACnet MS/TP link wiring
+
24
V
TBT
1
IM
C
0
1
2
3
4
5
6
7
8
9
x1
0
1
2
3
4
5
6
7
8
9
x10
0
1
2
3
4
5
6
7
8
9
x100
ADDRESS
ACT
LINK
2
1
RX
TX
IM
C
L3
L2
L1
STATU S
SC
+
Tracer
®
LINK 3LINK 2LINK 1
LINK 3LINK 2LINK 1
CONTROLLER
GROUND
ADDRESS
0
1
2
3
4
5
6
7
8
9
x1
0
1
2
3
4
5
6
7
8
9
x10
0
1
2
3
4
5
6
7
8
9
x100
AO
2/BI3
AO
1/BI2
ACTUATOR
BO
3
24
VAC
BO
2
24
VAC
BO
1
24
VAC
OUT
24
VAC
XFMR
RX
TX
LINK
RX
TX
SERVICE TOOL
+
24
VDC
IMC
STATU S
SERVI
C
E
UI
2
UI
1
BI1
AI
3
DAT
AI
2
SET
AI1
ZONE
210
Symbio
CONTROLLER
GROUND
ADDRESS
0
1
2
3
4
5
6
7
8
9
x1
0
1
2
3
4
5
6
7
8
9
x10
0
1
2
3
4
5
6
7
8
9
x100
AO
2/BI3
AO
1/BI2
ACTUATOR
BO
3
24
VAC
BO
2
24
VAC
BO
1
24
VAC
OUT
24
VAC
XFMR
RX
TX
LINK
RX
TX
SERVICE TOOL
+
24
VDC
IMC
STATU S
SERVI
C
E
UI
2
UI
1
BI1
AI
3
DAT
AI
2
SET
AI1
ZONE
210
Symbio
Symbio 210
Trane BACnet
Terminator
Symbio 210
Tracer SC+
Trane BACnet
Terminator
+
24
V
TBT