BAS-SVX084A-EN 23
Wiring Installation
The three values are joined together to form the BACnet device ID for the unit controller as shown
in the following table.
Device ID Assignment for BACnet/IP Devices
For devices connecting over BACnet/IP, Tracer SC+ calculates the device ID with the following:
• The BACnet network number for the BACnet/IP link. (This number can be changed by the user).
• The unit controller rotary switch value. (The Tracer SC+ rotary address is not used to calculate
BACnet/IP device IDs).
The following table shows this process using a Tracer UC600 unit controller.
Table 8. Calculating the BACnet/IP Device ID
For BACnet MS/TP Network numbers higher than 4190,TTrraacceerr SSCC++ will not be able follow
this scheme and will not propose a Device ID for the unit controller. The controller can be installed
with the Device ID number previously assigned to it.
Note: It is very important to avoid duplication of BACnet network numbers or device IDs.
Application Wiring
This section provides information about pre-configured wiring for the following applications:
• “Zone Sensor Wiring”
• “Duct Temperature Sensor Wiring,” p. 25
• “Binary Wiring,” p. 26
Note: For more details about mounting, wiring, and configuring wireless zone sensors, refer to the
section, “Additional Resources,” p. 75.
Zone Sensor Wiring
Zone Sensor Hard Wired Option
Depending on the zone sensor options used, a maximum of seven (7) wires may be required to run
from the Symbio
210 controller to the zone sensor. The zone sensor options are:
• Zone sensor (temperature only); Part Number X1351152801.
• Zone sensor with timed override (TOV) on/cancel button; Part Number X1351153001.
• Zone sensor with adjustable setpoint thumbwheel, Part Number X1351152901.
• Zone sensor with adjustable setpoint thumbwheel, timed override (TOV) on/cancel button;
Part Number X1351152701.
• Zone sensor with digital display; Part Number X1379088601.
Note: Display sensor has factory mounted communication module.
• Communications module; Part Number X1365146702, one (1) box of 12.
Table 7. Calculating the BACnet Device ID
Tracer SC+ rotary switch value (21) 0 2 1
Tracer SC+ BACnet MS/TP link number (1) 1
Unit controller rotary switch value (38) 0 3 8
BACnet Device ID 211038 0211038
BACnet network number Eth port 1 (1) 1
Unit controller rotary switch value (42) 0 4 2
BACnet/IP Device ID: 0142 0 1 0 4 2