EasyManua.ls Logo

Trane Symbio 210 - Page 30

Trane Symbio 210
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
30 BAS-SVX084A-EN
Controller LEDs
Each of the following codes is a two digit number following this pattern: First digit, 600mS pause,
Second digit, 2 second pause and then repeat the pattern.
Table 10. Marquee LED status and error codes
LED Blink Pattern Message Description Action by User
Green LED Blink
Pattern
Solid green light
No active alarms or
messages
None - normal operation
11 Load Field
Attempting to load the field kernel and device
tree from NAND flash.
None- normal operation
13 Boot Field
Successfully loaded the filed images and are
attempting to boot.
None- normal operation
14 Load Recover
Attempting to load the recover image from
NAND flash.
None- normal operation
16 Boot Recover
Successfully loaded the recovery image and
are attempting to boot.
None- normal operation
17 Recovery
Successfully booted into the recovery
partition.
None- normal operation
23 Field Format Reformatting the field file system. None- normal operation
28 Starting Update Starting the firmware update process. None- normal operation
29 Locating Firmware File Attempting to locate a firmware update file. None- normal operation
33 Validating Firmware
Validating the signature on the firmware
update file.
None- normal operation
35 Decrypting Firmware Decrypting the firmware update file. None- normal operation
36 Update Success Done performing the firmware update. None- normal operation
37 Clearing Database Clearing the database. None- normal operation
38 Validating Firmware
Validating the signature on the firmware
update file.
None- normal operation
41 Decrypting Firmware Decrypting the firmware update file. None- normal operation
43 Restoring Backup Restoring a database backup. None- normal operation
45 Force Database Clear
The user has 30 seconds to set the rotaries to
something other than 9-9-9 to start the
process of returning to factory defaults.
None- normal operation
46 Clear Done
Done returning the database to factory
defaults.
None- normal operation
47 Done
Done returning whatever process was started
(usually a forced recovery partition update).
None- normal operation
51 Backup Retored Database backup has been restored. None- normal operation
52 Updating Firmware Updating the firmware. None- normal operation
53 Firmware Updated Firmware was updated. None- normal operation
55 Updating Firmware Firmware is currently being updated. None- normal operation
56 Updating Kernel The kernel is currently being updated. None- normal operation
58 Updating Device Tree The kernel is currently being updated. None- normal operation
61 Updating Bootloader The bootloader is being updated. None- normal operation
63 Updating Recovery The recovery file system is being updated. None- normal operation

Table of Contents