Space Temperature Control Sequence of Operation
Constant Volume and Multi-Speed Fan Configuration
Normal Operation
The Symbio 700 has a single-loop (space temperature only) control sequence. The sequence is
PI-based (proportional, integral) and strives to maintain space temperature within 1F of the active
cooling and heating setpoints.
When Space Temperature Active > Space Temp Cooling Setpoint Status, the algorithm
calculates a need for cooling capacity to be energized.
When Space Temperature Active < Space Temp Heating Setpoint Status, the algorithm
calculates a need for heating capacity to be energized.
When Space Temp Heating Setpoint Status Space Temperature Active Space Temp
Cooling Setpoint Status:
The algorithm calculates a reduction in need for any active cooling or heating capacity if
ON.
If no cooling or heating capacity is active, cooling and heating capacity remains inactive.
Supply Fan Control
The supply fan is controlled “ON” 5 seconds before heating or cooling capacity is energized.
When heating or cooling capacity is de-energized, a supply fan off delay is applied based on
active capacity. For single-speed supply fan configured systems, the supply fan is controlled
“ON” during all cooling and heating sequences.
For multi-speed supply fan configured systems, the fan operates per the following:
Low speed when the supply fan is ON without active capacity (unless ON due to an override
function)
Low speed when the unit is operating at its minimum cooling stage
High speed when the unit is operating at its maximum cooling stage or while any heating
stages are active.