ACC-APG001A-EN
41
Table 21. Odyssey supported diagnostics and alarm relay functionality (continued)
Diagnostic/Alarm
Alarm Indicator
Diagnostic: Circuit 2 LPC Lockout
Y
Diagnostic: Compressor 1 Proving Lockout Y
Diagnostic: Compressor 2 Proving Lockout Y
Diagnostic: Compressor 1 Contactor Failure Y
Diagnostic: Compressor 2 Contactor Failure Y
Diagnostic: Circuit 1 LPC Trip N
Diagnostic: Circuit 2 LPC Trip N
Diagnostic: Comp 1 Proving Trip N
Diagnostic: Comp 2 Proving Trip N
Diagnostic: Maintenance Required
N
Coil Temperature Sensor 1 N
Coil Temperature Sensor 2 N
Coil Temperature Sensor 3 N
Discharge Air Temperature Local N
Outdoor Air Temperature Active
N
Outdoor Air Humidity Active N
Space CO2 Concentration Active N
Space Humidity Active N
Space Temperature Active N
Emergency and Ventilation Override
Table 22. Emergency and ventilation override
Inputs Outputs
Emergency Override
BAS
EOM
Supply
Fan On/
Off
Request
EOM
Supply
Fan
Speed
Request
EOM
Compres-
sor Cool
Stage
Request
EOM
Compres-
sor Heat
Stage
Request
EOM
Auxiliary
Heat
Stage
Request
Heat Cool
Mode
Status
Point State % Value Value Value Point
2 = EMERG_
PRESSURIZE
ON 100 0 0 0
Fan Only
3 = EMERG_
DEPRESSURIZE
OFF 0 0 0 0
Fan Only
4 = EMERG_PURGE
ON 100 0 0 0
Fan Only
5 = EMERG_SHUTDOWN
OFF 0 0 0 0 OFF
6 = EMERG_FIRE
OFF 0 0 0 0 OFF
1 = EMERG_NORMAL
Auto Auto Auto Auto Auto Auto
AAppppeennddiixx AA