16
BAS-SVU054A-EN
Figure 5. Symbio 700 indoor option module factory connections
Table 6. Symbio 700 indoor option module factory connections
Factory Connections
Function Pin #
Signal
P4 IMC Communication
1
24VAC In/Out
2 GND
3 IMC +
4 IMC -
P5 IMC Communication
1
24VAC In/Out
2 GND
3 IMC +
4 IMC -
P6
Electric Heat Stage 1
1
Electric Heat Stage 1 Output
2 GND
P7
Electric Heat Stage 2
1
Electric Heat Stage 2 Output
2 GND
P14
Discharge Air Temp
1
Discharge Air Temperature Input
2 GND
P16 FroStat
1 24Vac Out
2
FroStat Input
SW1 Module Address NA NA
SW2 Module Address NA NA