Trane Symbio 700 - Symbio 700 Field Connection Details

Trane Symbio 700
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BAS-SVU054A-EN
15
Table 5. Symbio 700 field connections
Customer
Connections
Function Pin #
Signal
J16
Demand Shed/Demand Limit Connection
1 24VAC Out
2
Demand Shed/Demand Limit Input
J17 BACnet Communication Connections
1 BACnet +
2 BACnet -
3 BACnet +
4 BACnet -
J18
Equipment Shutdown Input Connections
1 24VAC Out
2
Equipment Shutdown Input
J19 Zone Sensor Connections
1
Space/Zone Temperature
2 GND
3
Cool Setpoint
4 Mode
5
Heat Setpoint
6 GND
7 24VAC Out
J20
Occupancy Connections
1 24VAC Out
2
Occupancy Switch
J21 Thermostat Connections
1 24VAC Out
2 Y1
3
W1/O
4 G
5 W2
6 Y2
7 X2
8 1.5K Ohms Pull-down
9 GND
J22
Space CO2
1 24VDC Out
2
Input (0-10Vdc)
3 GND
J23
Space Humidity
1 24VDC Out
2
Input (4-20mA)
3 GND
4 NA